AC Contactor Not Pulling In - 10 Reasons Why

WEBVTT
Kind: captions
Language: en

00:00:00.030
so you've been working on your air
00:00:01.550 00:00:01.560 conditioner and you found the problem
00:00:03.050 00:00:03.060 and the problem is the contactor is not
00:00:05.480 00:00:05.490 pulling it but why why is it not pulling
00:00:08.030 00:00:08.040 it stay tuned to find out
00:00:17.470 00:00:17.480 [Music]
00:00:36.970 00:00:36.980 hey guys Jay here with one advice to be
00:00:39.830 00:00:39.840 on my how to fix your AC video the most
00:00:43.070 00:00:43.080 frequently asked question on there or
00:00:44.990 00:00:45.000 one of the most frequently asked is my
00:00:47.360 00:00:47.370 contactor is not pulling in what could
00:00:49.400 00:00:49.410 be causing that but before I get into
00:00:51.170 00:00:51.180 the 10 reasons why this could be
00:00:52.610 00:00:52.620 happening let's just quickly go over to
00:00:54.650 00:00:54.660 contact her and how it works so right
00:00:56.390 00:00:56.400 here we got our disconnect this is where
00:00:58.970 00:00:58.980 your 240 volts comes from you know our
00:01:01.610 00:01:01.620 circuit breaker panel is hooked up
00:01:03.710 00:01:03.720 straight to this thing it gets too hot
00:01:05.510 00:01:05.520 legs from here to 120 legs to get you to
00:01:08.090 00:01:08.100 40 and that goes right into your AC unit
00:01:11.030 00:01:11.040 through this whip and this whip will
00:01:12.830 00:01:12.840 typically have three wires inside of it
00:01:14.870 00:01:14.880 two hot legs on the ground and as you
00:01:17.450 00:01:17.460 can see that goes straight up into my
00:01:19.040 00:01:19.050 unit and also there's a thermostat wire
00:01:23.240 00:01:23.250 a lot of times they'll come from the
00:01:24.859 00:01:24.869 disconnect sometimes it'll come out with
00:01:26.780 00:01:26.790 the refrigerant pipes once in a while
00:01:28.969 00:01:28.979 it'll come out of the wall but that is
00:01:31.160 00:01:31.170 also routed straight to your AC
00:01:33.469 00:01:33.479 condenser unit so right here we got two
00:01:38.690 00:01:38.700 hot legs coming in and I'll just show
00:01:41.210 00:01:41.220 you quick with my meter the two hot legs
00:01:43.820 00:01:43.830 they come in straight from the
00:01:45.050 00:01:45.060 disconnect and into one side of the
00:01:47.480 00:01:47.490 contactor so if I put the black and red
00:01:50.180 00:01:50.190 wire right here they come from the
00:01:52.160 00:01:52.170 disconnect if I put my two leads on the
00:01:54.890 00:01:54.900 two screws here as you can see I got 245
00:01:59.179 00:01:59.189 volts and then power goes through the
00:02:01.820 00:02:01.830 contactor and comes out the other side
00:02:03.469 00:02:03.479 to power up the compressor and the fan
00:02:05.600 00:02:05.610 and what interrupts this is this little
00:02:08.120 00:02:08.130 plunger right here right now I won't
00:02:09.919 00:02:09.929 have any voltage because my AC is off
00:02:11.539 00:02:11.549 but your contactor coil contacts are
00:02:13.910 00:02:13.920 right here on either end where the blue
00:02:15.770 00:02:15.780 wire goes to and where the yellow wire
00:02:17.449 00:02:17.459 goes to so initially there's power at
00:02:20.870 00:02:20.880 the control board in your furnace or
00:02:22.400 00:02:22.410 your air handler that will send power to
00:02:25.069 00:02:25.079 your thermostat and when your thermostat
00:02:26.900 00:02:26.910 is calling for cooling or if you set it
00:02:28.819 00:02:28.829 for AC that will close a switch in the
00:02:31.160 00:02:31.170 thermostat and send power back down to
00:02:32.960 00:02:32.970 the control board and then the control
00:02:34.670 00:02:34.680 board will send power out to your AC
00:02:36.949 00:02:36.959 unit out here that will be your low
00:02:39.080 00:02:39.090 voltage the 24 volts so briefly let's
00:02:41.990 00:02:42.000 just look inside here again so that
00:02:43.970 00:02:43.980 thermostat wire that comes in to my unit
00:02:45.740 00:02:45.750 does brown wire usually it'll have two
00:02:48.920 00:02:48.930 wires
00:02:49.309 00:02:49.319 inside of it a red and a white as you
00:02:52.130 00:02:52.140 can see the red ties in with a wire nut
00:02:54.860 00:02:54.870 into the blue wire and my blue wire is
00:02:57.050 00:02:57.060 that wire right there going to the
00:02:58.849 00:02:58.859 contactor coil on one side but my white
00:03:02.059 00:03:02.069 wire coming out of the thermostat wire
00:03:05.229 00:03:05.239 goes into another red thermostat wire
00:03:08.149 00:03:08.159 and then goes into this white insulator
00:03:11.869 00:03:11.879 wire right here which goes back out into
00:03:14.330 00:03:14.340 my power saver switch right here so
00:03:17.899 00:03:17.909 really what that is is basically this
00:03:20.179 00:03:20.189 power saver switch is in series with my
00:03:22.670 00:03:22.680 contactor coil sometimes ACS will have
00:03:25.640 00:03:25.650 nothing in series with the contactor
00:03:27.470 00:03:27.480 coil that just means that the red and
00:03:29.899 00:03:29.909 white wire will go straight to the
00:03:31.939 00:03:31.949 contactor whereas in my case it goes
00:03:35.420 00:03:35.430 into the white wire it goes through that
00:03:37.220 00:03:37.230 power saver switch and then comes back
00:03:38.689 00:03:38.699 out it goes into this wire nut turns
00:03:41.059 00:03:41.069 into this yellow wire and goes on the
00:03:42.860 00:03:42.870 other side of the contactor all right so
00:03:45.530 00:03:45.540 reason number one wire contactor plunger
00:03:47.780 00:03:47.790 may not be pulling in is because your
00:03:49.640 00:03:49.650 furnace power switch is off maybe you
00:03:51.709 00:03:51.719 were changing the filter and it got
00:03:53.209 00:03:53.219 bumped off or maybe some kids were
00:03:54.890 00:03:54.900 playing around and turned it off in fact
00:03:56.899 00:03:56.909 while I'm on that topic if the inside
00:03:59.300 00:03:59.310 fan inside your house if the blower
00:04:01.039 00:04:01.049 motor is not working then you should put
00:04:03.649 00:04:03.659 the contactor and hold and go figure out
00:04:05.539 00:04:05.549 why your fans not working first before
00:04:07.189 00:04:07.199 you deal with the contactor if your
00:04:09.050 00:04:09.060 furnace is not getting power if that
00:04:10.699 00:04:10.709 power switches off that means that
00:04:12.499 00:04:12.509 control board is not getting power
00:04:13.580 00:04:13.590 therefore it's not going to send
00:04:14.990 00:04:15.000 anything outside to the contactor and
00:04:16.909 00:04:16.919 reason number two is a condensate
00:04:19.009 00:04:19.019 overflow switch especially if you live
00:04:21.439 00:04:21.449 in Florida that seems to be a common
00:04:23.120 00:04:23.130 problem there or if you have an attic
00:04:25.159 00:04:25.169 unit those will almost all the time have
00:04:27.740 00:04:27.750 a condensate overflow switch so that
00:04:30.050 00:04:30.060 thing will basically interrupt the power
00:04:31.610 00:04:31.620 going out to your contactor if your
00:04:34.159 00:04:34.169 drain line is plugged and the water is
00:04:36.560 00:04:36.570 backing up that float switch will the
00:04:38.240 00:04:38.250 water will go up and trip the switch and
00:04:39.920 00:04:39.930 kill the power to it that way you don't
00:04:41.689 00:04:41.699 have water overflowing and damaging your
00:04:43.760 00:04:43.770 ceilings and everything so if you have a
00:04:45.649 00:04:45.659 condensate overflow switch check that
00:04:47.959 00:04:47.969 out and make sure your drain is not
00:04:49.550 00:04:49.560 plugged up and number three is a bad
00:04:51.740 00:04:51.750 thermostat or a thermostat working
00:04:53.570 00:04:53.580 incorrectly now I say working correctly
00:04:55.879 00:04:55.889 because perhaps it could just be dead or
00:04:58.850 00:04:58.860 weak batteries when batteries are weak
00:05:00.980 00:05:00.990 your display will still be on
00:05:03.050 00:05:03.060 that low battery symbol will not always
00:05:05.330 00:05:05.340 appear so the display will be on but the
00:05:07.640 00:05:07.650 batteries don't have enough power to
00:05:09.260 00:05:09.270 close the switch to make a call for
00:05:11.030 00:05:11.040 cooling so if your thermostat has
00:05:12.470 00:05:12.480 batteries try replacing those another
00:05:14.990 00:05:15.000 thing I've seen is the connectors behind
00:05:17.480 00:05:17.490 there or loose or sometimes a wires just
00:05:19.520 00:05:19.530 broken off altogether so ploy your
00:05:21.409 00:05:21.419 thermostat off the wall and just try
00:05:23.360 00:05:23.370 gently tugging on each wire and make
00:05:25.129 00:05:25.139 sure that each one of them is making a
00:05:26.720 00:05:26.730 good connection and if you have recently
00:05:28.129 00:05:28.139 replaced your thermostat and you have an
00:05:30.440 00:05:30.450 R and an RC pin make sure you have a
00:05:33.050 00:05:33.060 jumper between R and RC because R means
00:05:36.230 00:05:36.240 power and RC means power for cooling so
00:05:39.290 00:05:39.300 if you don't have a jumper between the
00:05:40.430 00:05:40.440 two you have no power for cooling and of
00:05:42.440 00:05:42.450 course the thermostat could just simply
00:05:44.270 00:05:44.280 be bad and an easy way to find out if
00:05:46.250 00:05:46.260 it's bad or not is just to bypass it
00:05:48.230 00:05:48.240 either at the thermostat or at the
00:05:49.879 00:05:49.889 control board I think the best if you're
00:05:52.159 00:05:52.169 trying to find out if the thermostat is
00:05:53.420 00:05:53.430 bad or not is to bypass it at the
00:05:55.430 00:05:55.440 thermostat by putting a little jumper
00:05:57.230 00:05:57.240 between R and Y if it kicks on you know
00:06:00.140 00:06:00.150 the thermostat is the problem if it
00:06:01.700 00:06:01.710 doesn't then there's something else
00:06:03.200 00:06:03.210 going on and I have a video of how to
00:06:05.300 00:06:05.310 bypass the thermostat and how to bypass
00:06:07.370 00:06:07.380 the thermostat at the control board in
00:06:09.050 00:06:09.060 my AC fixing playlist so if you want
00:06:11.150 00:06:11.160 check those out
00:06:11.990 00:06:12.000 and reason number four is bad wiring and
00:06:14.600 00:06:14.610 what I mean by that is bad wire
00:06:16.640 00:06:16.650 connectors bare wires corroded wires
00:06:19.540 00:06:19.550 broken or melted wires so investigate
00:06:23.240 00:06:23.250 all your wires especially the low
00:06:25.219 00:06:25.229 voltage you know like the thermostat
00:06:27.800 00:06:27.810 wires that I showed you in the beginning
00:06:28.880 00:06:28.890 of the video look at all those for any
00:06:31.100 00:06:31.110 breaks or bare spots then go inside at
00:06:33.440 00:06:33.450 the furnace where the control board is
00:06:35.150 00:06:35.160 where those thermostat wires go into it
00:06:36.950 00:06:36.960 check all of them out make sure there's
00:06:38.960 00:06:38.970 nothing broken and while you're at the
00:06:40.790 00:06:40.800 control board take out that 3 amp fuse
00:06:43.100 00:06:43.110 make sure that thing's not blown if your
00:06:44.870 00:06:44.880 3 amp fuse is blown replace it but
00:06:47.000 00:06:47.010 before you do usually those 3 amp fuses
00:06:49.310 00:06:49.320 blow because there's a short somewhere
00:06:50.960 00:06:50.970 so investigate your wires before
00:06:52.550 00:06:52.560 replacing a blown fuse this AC season I
00:06:55.190 00:06:55.200 had two special cases one was where a
00:06:57.500 00:06:57.510 dog actually chewed through the
00:06:59.029 00:06:59.039 thermostat wire outside and another one
00:07:01.310 00:07:01.320 the customer was going around with a
00:07:02.990 00:07:03.000 weed whacker and didn't even notice that
00:07:04.550 00:07:04.560 he had chopped his thermostat wire in
00:07:06.500 00:07:06.510 half so of course nothing was working
00:07:08.029 00:07:08.039 but anyways do investigate your
00:07:09.740 00:07:09.750 thermostat wires outside and inside for
00:07:11.990 00:07:12.000 any kind of damages and reason number 5
00:07:14.180 00:07:14.190 is a bad 5
00:07:15.580 00:07:15.590 delay board now my unit does not have
00:07:18.100 00:07:18.110 that on here so I can't show you it but
00:07:20.620 00:07:20.630 it's just a little either a black box or
00:07:22.840 00:07:22.850 a little control board at your outside
00:07:24.909 00:07:24.919 unit basically what that does is prevent
00:07:27.550 00:07:27.560 your AC unit from short cycling like if
00:07:30.190 00:07:30.200 you have a power outage or something
00:07:31.390 00:07:31.400 like that your AC unit if it turns off
00:07:33.970 00:07:33.980 that thing will prevent it from turning
00:07:35.440 00:07:35.450 right back on right away or if
00:07:37.060 00:07:37.070 somebody's playing with the thermostat
00:07:38.470 00:07:38.480 inside the house it won't let you turn
00:07:40.540 00:07:40.550 the AC on and off on and off because
00:07:42.460 00:07:42.470 that's bad for the compressor but
00:07:44.140 00:07:44.150 sometimes that board goes bad so power
00:07:46.570 00:07:46.580 goes into it because it's in series with
00:07:48.430 00:07:48.440 the contactor but it never comes back
00:07:50.409 00:07:50.419 out to energize that contactor coil and
00:07:52.900 00:07:52.910 pull it in if it's just a simple board
00:07:54.700 00:07:54.710 what you can do is just take it out of
00:07:56.320 00:07:56.330 the circuit so the thermostat wires
00:07:58.450 00:07:58.460 coming from inside the house just route
00:08:00.670 00:08:00.680 those straight to your contactor coil
00:08:02.620 00:08:02.630 turn your AC back on and if it turns on
00:08:04.930 00:08:04.940 and everything works great then you know
00:08:06.580 00:08:06.590 that that board was the problem and
00:08:08.110 00:08:08.120 reason number six is a bad control board
00:08:11.050 00:08:11.060 in the furnace or your air handler or
00:08:13.240 00:08:13.250 maybe it's a fan relay
00:08:14.680 00:08:14.690 maybe there's a burnt-out spot or
00:08:16.360 00:08:16.370 there's a relay in there that went bad
00:08:17.800 00:08:17.810 but if it's not sending power to the
00:08:19.870 00:08:19.880 outdoor unit an easy way to check that
00:08:22.210 00:08:22.220 is to take your meter set it to voltage
00:08:24.340 00:08:24.350 and with your leads at the furnace
00:08:26.260 00:08:26.270 control board with the power on check
00:08:28.960 00:08:28.970 between Y and C you should have 27 volts
00:08:32.409 00:08:32.419 going outside if you don't have 27 volts
00:08:35.140 00:08:35.150 going outside then there's a problem
00:08:37.089 00:08:37.099 inside either with the control board or
00:08:39.130 00:08:39.140 with that thermostat and I have separate
00:08:41.050 00:08:41.060 videos of how to troubleshoot both of
00:08:43.089 00:08:43.099 those and while I'm talking about that
00:08:45.100 00:08:45.110 another easy way to check that is take
00:08:48.490 00:08:48.500 your two meter lead set it to voltage
00:08:49.930 00:08:49.940 and then your thermostat wire that comes
00:08:51.820 00:08:51.830 out of the house and into your unit the
00:08:53.380 00:08:53.390 brown wire that has the red and the
00:08:55.329 00:08:55.339 white wire put your meter leads on the
00:08:57.460 00:08:57.470 red and the white if it has 27 volts
00:08:59.710 00:08:59.720 coming out that means whatever is
00:09:01.780 00:09:01.790 interrupting your power the low voltage
00:09:03.490 00:09:03.500 is going to be outside if you don't have
00:09:06.010 00:09:06.020 27 volts or 24 volts that means the
00:09:08.650 00:09:08.660 problem is inside the house so if you
00:09:10.720 00:09:10.730 have voltage out heater problems out
00:09:12.579 00:09:12.589 here no voltage out here problems inside
00:09:14.949 00:09:14.959 and reason number seven is a bad power
00:09:18.970 00:09:18.980 saver switch this box right here not all
00:09:21.970 00:09:21.980 houses have this but if you do generally
00:09:24.790 00:09:24.800 it'll be by your disconnect and what
00:09:26.800 00:09:26.810 that does is on really hot
00:09:29.070 00:09:29.080 The Electric Company cycles people on
00:09:30.990 00:09:31.000 and off sporadically so not everybody is
00:09:33.240 00:09:33.250 running their AC at the same time and
00:09:35.130 00:09:35.140 they give you like 10 or 15 bucks off a
00:09:37.200 00:09:37.210 month for doing that but sometimes this
00:09:39.510 00:09:39.520 power saver switch can become defective
00:09:41.280 00:09:41.290 so power goes into it but it never comes
00:09:43.680 00:09:43.690 back out to your contactor if you think
00:09:45.510 00:09:45.520 the power saver switch is your issue I
00:09:47.460 00:09:47.470 have a video specifically just for the
00:09:49.890 00:09:49.900 power saver switch how you can bypass to
00:09:51.840 00:09:51.850 check if that's your problem or not and
00:09:53.760 00:09:53.770 then call the electric company and have
00:09:55.140 00:09:55.150 them fix their box and reason number
00:09:57.390 00:09:57.400 eight is a tripped high pressure switch
00:10:00.000 00:10:00.010 or a low pressure switch or maybe they
00:10:02.190 00:10:02.200 could be bad - if you're not sure what
00:10:04.290 00:10:04.300 I'm talking about an easy way to see if
00:10:06.180 00:10:06.190 you have one or not one is to look at
00:10:08.250 00:10:08.260 your wiring diagram on the back of your
00:10:09.870 00:10:09.880 door and two is to just look on top of
00:10:12.000 00:10:12.010 your unit and you have two refrigerant
00:10:14.100 00:10:14.110 pipes going out of your compressor one
00:10:15.780 00:10:15.790 is thick one is thin see if there's
00:10:17.940 00:10:17.950 anything attached to those pipes if you
00:10:19.770 00:10:19.780 look from the top
00:10:20.430 00:10:20.440 the low pressure switch is going to be
00:10:22.410 00:10:22.420 mounted to your thicker pipe and then
00:10:25.170 00:10:25.180 the high pressure switch will be mounted
00:10:26.880 00:10:26.890 to the discharge line or the thinner
00:10:28.710 00:10:28.720 pipe they usually look like black
00:10:30.600 00:10:30.610 cylinders or a black disc with two wires
00:10:33.300 00:10:33.310 coming out of it and their function is
00:10:35.310 00:10:35.320 to interrupt the power if your
00:10:37.050 00:10:37.060 refrigerant pressures or freon pressures
00:10:39.150 00:10:39.160 are either too high or too low in the
00:10:41.400 00:10:41.410 system a lot of times the high pressure
00:10:43.530 00:10:43.540 switch on the thin line will be
00:10:45.630 00:10:45.640 resettable it'll have a little red
00:10:47.220 00:10:47.230 button on it you can press that and if
00:10:49.530 00:10:49.540 it presses in you hear a click that
00:10:51.420 00:10:51.430 means that was tripped and you just
00:10:52.650 00:10:52.660 reset it and your AC will start working
00:10:54.900 00:10:54.910 normally but that also means that your
00:10:56.910 00:10:56.920 pressures for some reason got too high a
00:10:58.800 00:10:58.810 lot of times the reason for that is
00:11:00.990 00:11:01.000 because your condenser coil is dirty so
00:11:03.329 00:11:03.339 even if it looks clean how it holds it
00:11:05.370 00:11:05.380 down and spray it down make sure it's
00:11:06.690 00:11:06.700 clean and if it looks dirty well then of
00:11:08.940 00:11:08.950 course it's dirty as for the low
00:11:10.440 00:11:10.450 pressure switch if that's tripped those
00:11:12.660 00:11:12.670 are usually not resettable that just
00:11:14.820 00:11:14.830 means your refrigerant levels are very
00:11:16.410 00:11:16.420 low oftentimes when those are tripping
00:11:19.079 00:11:19.089 your unit will turn on it'll run for a
00:11:21.240 00:11:21.250 little bit and then turn back off turn
00:11:23.310 00:11:23.320 back on run for a little bit turn back
00:11:25.110 00:11:25.120 off
00:11:25.530 00:11:25.540 if the low-pressure trip is switched and
00:11:27.720 00:11:27.730 it's not resetting automatically that
00:11:29.550 00:11:29.560 means your freon pressures are very low
00:11:31.290 00:11:31.300 to check that you can either disconnect
00:11:33.300 00:11:33.310 the wires and omit out for resistance
00:11:35.010 00:11:35.020 you can check voltage to see if you have
00:11:37.290 00:11:37.300 voltage coming in and voltage coming out
00:11:39.030 00:11:39.040 or you can bypass it and see if the unit
00:11:41.550 00:11:41.560 will turn on without
00:11:42.420 00:11:42.430 but that is of course just for testing
00:11:44.280 00:11:44.290 purposes you do not want to leave it by
00:11:46.019 00:11:46.029 pass because there's a reason why it
00:11:47.730 00:11:47.740 tripped in the first place but once in a
00:11:49.590 00:11:49.600 while
00:11:50.070 00:11:50.080 the high pressure switch or low pressure
00:11:51.690 00:11:51.700 switch are just simply bad I don't have
00:11:54.360 00:11:54.370 those too often but once in a while I'll
00:11:56.010 00:11:56.020 come across the high pressure switch for
00:11:57.600 00:11:57.610 example that's just stuck open and it
00:11:59.820 00:11:59.830 will not close but when I check the
00:12:01.350 00:12:01.360 pressures of the freon everything is
00:12:03.540 00:12:03.550 good in that case you just need to
00:12:05.100 00:12:05.110 replace that high pressure switch and
00:12:06.660 00:12:06.670 you'll be good to go
00:12:07.860 00:12:07.870 but anyway I'm spending a little too
00:12:09.240 00:12:09.250 much time in the pressure switches those
00:12:10.980 00:12:10.990 tend to be a little bit more complicated
00:12:12.810 00:12:12.820 you might be better off calling a tech
00:12:14.670 00:12:14.680 at that point and reason number nine why
00:12:17.730 00:12:17.740 your contactor might not be pulling in
00:12:19.260 00:12:19.270 is a bad contactor itself now to check
00:12:22.260 00:12:22.270 that it's pretty easy all you got to do
00:12:23.730 00:12:23.740 is set your meter to voltage and put
00:12:26.190 00:12:26.200 your muna leads on either end of the
00:12:27.570 00:12:27.580 contactor coil where that yellow wire
00:12:29.280 00:12:29.290 and blue wire came in and mine and see
00:12:31.650 00:12:31.660 if you have 27 volts there if there's
00:12:33.570 00:12:33.580 voltage going to the contactor
00:12:35.250 00:12:35.260 yep that little plunger is not pulling
00:12:37.199 00:12:37.209 in that means you have a bad contactor
00:12:39.120 00:12:39.130 coil you could also disconnect the wires
00:12:40.920 00:12:40.930 and check for resistance if it's a while
00:12:42.900 00:12:42.910 it's bad as well and another thing I
00:12:44.850 00:12:44.860 should mention especially if you are
00:12:46.260 00:12:46.270 down south in like Texas and Arizona
00:12:47.940 00:12:47.950 make sure you check if your contact your
00:12:50.670 00:12:50.680 contacts have any bugs or ants inside of
00:12:53.790 00:12:53.800 them because they could be preventing
00:12:55.140 00:12:55.150 that plunger from pulling it and reason
00:12:57.420 00:12:57.430 number 10 and the final reason is a bad
00:12:59.550 00:12:59.560 transformer not a lot of air
00:13:01.590 00:13:01.600 conditioners will have a transformer or
00:13:03.840 00:13:03.850 at least in Minnesota they don't I don't
00:13:05.220 00:13:05.230 know maybe some other states have a lot
00:13:06.630 00:13:06.640 of them but if your unit has a
00:13:08.250 00:13:08.260 transformer there's a chance that that's
00:13:10.050 00:13:10.060 bad as well and that's what's causing
00:13:11.579 00:13:11.589 that so check if your Transformers bad
00:13:13.470 00:13:13.480 you would just have to look up a video
00:13:14.699 00:13:14.709 on how to mount a transformer and their
00:13:17.430 00:13:17.440 resistance and just see if you have the
00:13:18.930 00:13:18.940 right readings if you have o/l or open
00:13:21.240 00:13:21.250 line instead of a reading well then you
00:13:23.100 00:13:23.110 know for sure that your transformer is
00:13:24.600 00:13:24.610 bad but if you have a burnt-out
00:13:26.130 00:13:26.140 transformer make sure you replace your
00:13:28.590 00:13:28.600 contactor first because your contactor
00:13:31.140 00:13:31.150 may have been the reason why your
00:13:32.519 00:13:32.529 transformer burned out so if you have a
00:13:34.740 00:13:34.750 bad transformer replace both the
00:13:36.930 00:13:36.940 contactor and the transformer and you
00:13:38.790 00:13:38.800 should be good to go and that covers
00:13:40.889 00:13:40.899 just about all of them I did not cover
00:13:42.810 00:13:42.820 anything about communicating systems
00:13:44.280 00:13:44.290 because that's like a whole nother beast
00:13:46.590 00:13:46.600 you're better off calling a technician
00:13:48.180 00:13:48.190 at that point what I mean by
00:13:49.560 00:13:49.570 communicating systems is instead of like
00:13:52.110 00:13:52.120 your normal thermostat terminal strip on
00:13:54.420 00:13:54.430 your thermostat and control
00:13:55.650 00:13:55.660 bored and outside like the G the RW the
00:13:58.890 00:13:58.900 Y all you're gonna have is a green
00:14:00.660 00:14:00.670 little molex plug that says ABCD those
00:14:03.870 00:14:03.880 are harder to troubleshoot and diagnose
00:14:05.730 00:14:05.740 so yeah like I was saying you're better
00:14:07.560 00:14:07.570 off just calling a technician at that
00:14:09.030 00:14:09.040 point if you have that kind of system
00:14:10.620 00:14:10.630 well guys and those were the ten reasons
00:14:12.180 00:14:12.190 why your contactor might not be pulling
00:14:13.950 00:14:13.960 in I hope you found this video useful if
00:14:15.990 00:14:16.000 you have something to add or if you have
00:14:17.490 00:14:17.500 some reasons that I missed please do so
00:14:19.380 00:14:19.390 in the comments below so everybody else
00:14:21.030 00:14:21.040 can learn from that as well
00:14:22.290 00:14:22.300 a lot of times the best part of the
00:14:23.670 00:14:23.680 video is the commentary below so make
00:14:25.800 00:14:25.810 sure you check that out thank you so
00:14:27.210 00:14:27.220 much for watching this video don't
00:14:28.620 00:14:28.630 forget to mash that like button under
00:14:29.940 00:14:29.950 way out and we'll see you next time