Boiler_Condensate and Feed Water System_Principle_Components_Problemsشرح نظام المتكاثف والمياه ا

WEBVTT
Kind: captions
Language: en

00:00:01.129
the main steam system in a power plant
00:00:03.970 00:00:03.980 controls the flow of high-temperature
00:00:06.349 00:00:06.359 high-pressure steam as it moves from a
00:00:09.140 00:00:09.150 boiler to a turbine and is used to drive
00:00:11.509 00:00:11.519 a generator to increase overall plant
00:00:14.810 00:00:14.820 efficiency some steam is extracted from
00:00:17.390 00:00:17.400 the turbine and used to heat the feed
00:00:19.700 00:00:19.710 water for the boiler the rest of the
00:00:22.519 00:00:22.529 steam is exhausted from the turbine to a
00:00:24.560 00:00:24.570 main condenser condensate from the main
00:00:28.310 00:00:28.320 condenser goes through the condensate
00:00:30.560 00:00:30.570 system and becomes feed water that
00:00:34.280 00:00:34.290 returns to the boiler through the feed
00:00:36.080 00:00:36.090 water system in this way the condensate
00:00:39.799 00:00:39.809 in feed water systems work together to
00:00:42.200 00:00:42.210 supply water at the proper rate to
00:00:44.540 00:00:44.550 support normal boiler operation because
00:00:47.869 00:00:47.879 the functions of these two systems are
00:00:49.729 00:00:49.739 interdependent they're often considered
00:00:52.279 00:00:52.289 one system the condensate and feed water
00:00:55.250 00:00:55.260 system to maintain normal operation of a
00:00:59.750 00:00:59.760 power plants boiler the water going into
00:01:02.779 00:01:02.789 the boiler must be equal to the amount
00:01:05.450 00:01:05.460 of steam that leaves the boiler and
00:01:07.640 00:01:07.650 enters the main steam system keeping the
00:01:11.120 00:01:11.130 boiler supplied with the proper amount
00:01:12.980 00:01:12.990 of water is the job of the condensate
00:01:15.590 00:01:15.600 and feed water system this simplified
00:01:19.070 00:01:19.080 illustration shows the arrangement or
00:01:21.260 00:01:21.270 layout of some of the major components
00:01:23.060 00:01:23.070 of a typical condensate in feed water
00:01:25.789 00:01:25.799 system and a main steam system included
00:01:29.719 00:01:29.729 are a boiler a turbine a main condenser
00:01:36.109 00:01:36.119 a feed water storage tank and various
00:01:41.899 00:01:41.909 pumps heaters valves and piping the area
00:01:50.270 00:01:50.280 between the main condenser and the
00:01:52.100 00:01:52.110 suction of this pump the boiler feed
00:01:54.800 00:01:54.810 pump is the condensate side of the
00:01:57.530 00:01:57.540 system we'll look at it first additional
00:02:02.899 00:02:02.909 systems are often connected to the basic
00:02:05.179 00:02:05.189 condensate system that we've just seen
00:02:07.900 00:02:07.910 typically a chemical addition system is
00:02:11.300 00:02:11.310 connected to the condensate system
00:02:13.770 00:02:13.780 in some cases however a chemical
00:02:16.050 00:02:16.060 addition system may be connected to both
00:02:18.360 00:02:18.370 the condensate side and the feed water
00:02:20.880 00:02:20.890 side of the system or just to the feed
00:02:23.430 00:02:23.440 water side in any case the chemical
00:02:26.580 00:02:26.590 addition system has equipment for adding
00:02:28.920 00:02:28.930 chemicals that minimize corrosion and
00:02:31.440 00:02:31.450 control the pH of the condensate or
00:02:33.870 00:02:33.880 water pH is a measure of how acid or
00:02:37.680 00:02:37.690 alkaline the water is usually a
00:02:40.920 00:02:40.930 condensate system also has a make up
00:02:43.620 00:02:43.630 water system that is connected to the
00:02:45.840 00:02:45.850 hot well the makeup water system
00:02:48.510 00:02:48.520 includes a condensate storage tank and
00:02:51.229 00:02:51.239 purification equipment that is used to
00:02:53.520 00:02:53.530 add pure water to the condensate system
00:02:56.390 00:02:56.400 the added water compensates for water
00:02:59.610 00:02:59.620 losses that may occur during normal
00:03:01.949 00:03:01.959 system operation or from leaks finally
00:03:05.820 00:03:05.830 various components in the condensate
00:03:08.040 00:03:08.050 system are also equipped with
00:03:09.840 00:03:09.850 instruments that measure pressures
00:03:11.820 00:03:11.830 temperatures levels and flows these
00:03:15.900 00:03:15.910 measurements are used in control loops
00:03:18.150 00:03:18.160 that regulate operation of the system
00:03:20.340 00:03:20.350 and give operators an indication of how
00:03:22.949 00:03:22.959 the system is functioning we've covered
00:03:26.490 00:03:26.500 the condensate side of the condensate in
00:03:28.920 00:03:28.930 feed water system next we'll look at the
00:03:32.759 00:03:32.769 feed water side now let's trace the flow
00:03:38.460 00:03:38.470 of feed water through the system
00:03:40.170 00:03:40.180 starting with the boiler feed booster
00:03:42.750 00:03:42.760 pumps not all feed water systems have
00:03:45.960 00:03:45.970 boiler feed booster pumps but in this
00:03:48.509 00:03:48.519 case there are three of them these pumps
00:03:51.750 00:03:51.760 increase the pressure of the feed water
00:03:53.699 00:03:53.709 coming from the intermediate pressure
00:03:55.500 00:03:55.510 heaters and send the water to the boiler
00:03:58.500 00:03:58.510 feed pumps in this example there are two
00:04:02.490 00:04:02.500 boiler feed pumps they increase the feed
00:04:05.970 00:04:05.980 water pressure further so it's high
00:04:08.160 00:04:08.170 enough for the water to move through the
00:04:10.140 00:04:10.150 downstream components from the boiler
00:04:13.590 00:04:13.600 feed pumps the feed water enters a
00:04:15.810 00:04:15.820 series or train of high pressure feed
00:04:18.719 00:04:18.729 water heaters after passing through
00:04:21.599 00:04:21.609 these heaters the feed water is ready to
00:04:24.480 00:04:24.490 go to the boiler
00:04:27.180 00:04:27.190 feedwater regulating valve controls the
00:04:30.300 00:04:30.310 flow of feed water from the
00:04:31.680 00:04:31.690 high-pressure heaters into the boilers
00:04:33.870 00:04:33.880 economizer the economizer is the section
00:04:38.340 00:04:38.350 of the boiler where combustion gases
00:04:40.440 00:04:40.450 leaving the boiler are used to preheat
00:04:43.140 00:04:43.150 the feed water that is entering the
00:04:45.150 00:04:45.160 boiler finally as with the condensate
00:04:49.020 00:04:49.030 system the feed water system also
00:04:51.360 00:04:51.370 includes instruments for level flow
00:04:54.230 00:04:54.240 temperature and pressure indication and
00:04:57.060 00:04:57.070 control one more system that we need to
00:05:03.360 00:05:03.370 look at is the extraction steam system
00:05:06.330 00:05:06.340 which serves both sides of the
00:05:08.460 00:05:08.470 condensate and feed water system steam
00:05:11.400 00:05:11.410 is extracted from the turbine and used
00:05:13.950 00:05:13.960 as the heating fluid in heaters
00:05:15.810 00:05:15.820 throughout the condensate and feed water
00:05:17.760 00:05:17.770 system steam from a high pressure
00:05:20.910 00:05:20.920 section of the turbine is generally used
00:05:23.670 00:05:23.680 in the high-pressure feed water heaters
00:05:26.600 00:05:26.610 steam from the intermediate pressure
00:05:29.040 00:05:29.050 00:05:31.680 00:05:31.690 in the intermediate pressure heaters and
00:05:33.840 00:05:33.850 in the deaerator
00:05:35.750 00:05:35.760 steam from the low-pressure section of
00:05:38.460 00:05:38.470 the turbine is used in the low pressure
00:05:40.530 00:05:40.540 heaters heating the condensate in feed
00:05:43.530 00:05:43.540 water with the steam from the different
00:05:45.450 00:05:45.460 sections of the turbine increases
00:05:47.820 00:05:47.830 overall plant efficiency
00:05:51.409 00:05:51.419 although the examples that we've looked
00:05:53.880 00:05:53.890 at are typical layouts there are also
00:05:56.700 00:05:56.710 many other ways that a condensate and
00:05:59.040 00:05:59.050 feed water system can be arranged you'll
00:06:02.159 00:06:02.169 need to look at your plants piping and
00:06:04.170 00:06:04.180 Instrumentation diagrams to check the
00:06:06.750 00:06:06.760 exact layout of the system in your
00:06:08.670 00:06:08.680 facility although the exact arrangement
00:06:13.890 00:06:13.900 of components in a condensate and feed
00:06:16.200 00:06:16.210 water system can vary several pieces of
00:06:19.200 00:06:19.210 equipment are common to most systems in
00:06:22.080 00:06:22.090 this part we'll look at the major
00:06:24.060 00:06:24.070 components of a typical condensate in
00:06:26.520 00:06:26.530 feed water system we'll begin with the
00:06:30.090 00:06:30.100 hot well the hot well is the bottom
00:06:32.850 00:06:32.860 section of the main condenser condensate
00:06:36.090 00:06:36.100 from the main condenser collects here
00:06:38.190 00:06:38.200 and is then sent on through the con
00:06:40.500 00:06:40.510 seyton feed water system where the
00:06:42.810 00:06:42.820 temperature and pressure of the
00:06:44.190 00:06:44.200 condensate are gradually increased sight
00:06:48.000 00:06:48.010 glasses indicate the level in the hot
00:06:50.130 00:06:50.140 well a level control loop is used to
00:06:53.490 00:06:53.500 maintain the correct level of condensate
00:06:56.720 00:06:56.730 maintaining the correct level in the hot
00:06:59.040 00:06:59.050 well is critical for proper operation of
00:07:01.920 00:07:01.930 the main condenser also a low level in
00:07:05.820 00:07:05.830 the hot well could cause the condensate
00:07:08.010 00:07:08.020 pumps downstream to lose their prime and
00:07:10.740 00:07:10.750 be damaged a condensate and feed water
00:07:16.350 00:07:16.360 system also has several condensers and
00:07:19.440 00:07:19.450 heaters most of these are some type of
00:07:22.950 00:07:22.960 shell and tube heat exchanger for
00:07:25.520 00:07:25.530 example the initial warming of the
00:07:28.320 00:07:28.330 condensate from mehat well is achieved
00:07:31.050 00:07:31.060 by using the condensate as the cooling
00:07:33.660 00:07:33.670 fluid in condensers glands steam
00:07:37.350 00:07:37.360 condensers recover heat from the steam
00:07:39.600 00:07:39.610 used in the plants gland steam system
00:07:43.040 00:07:43.050 error ejected n sirs recover heat from
00:07:46.890 00:07:46.900 the steam in the main condensers air
00:07:48.750 00:07:48.760 removal system both of these types of
00:07:52.590 00:07:52.600 condensers are usually shell and tube
00:07:55.020 00:07:55.030 heat exchangers a shell and tube heat
00:07:57.870 00:07:57.880 exchanger has a shell or casing with a
00:08:01.950 00:08:01.960 bundle of tubes inside the area that's
00:08:05.550 00:08:05.560 within the shell and outside of the
00:08:07.650 00:08:07.660 tubes is called the shell side of the
00:08:10.110 00:08:10.120 heat exchanger the area that's within
00:08:13.530 00:08:13.540 the tubes is called the tube side of the
00:08:16.170 00:08:16.180 heat exchanger the heat exchangers that
00:08:20.010 00:08:20.020 are used as condensers in the condensate
00:08:22.620 00:08:22.630 and feed water system have condensate in
00:08:25.590 00:08:25.600 the tube side and steam from the gland
00:08:29.100 00:08:29.110 steam system or the air removal system
00:08:31.740 00:08:31.750 in the shell side during the heat
00:08:34.830 00:08:34.840 exchange process the steam is cooled and
00:08:37.770 00:08:37.780 the condensate in the condensers is
00:08:39.960 00:08:39.970 heated you tube shell and tube heat
00:08:43.500 00:08:43.510 exchangers are used as heaters to heat
00:08:46.560 00:08:46.570 the condensate and feed water that moves
00:08:48.600 00:08:48.610 through the system
00:08:51.050 00:08:51.060 condensate or feed water flows through
00:08:53.640 00:08:53.650 the two
00:08:54.120 00:08:54.130 side of the heater and extraction steam
00:08:57.480 00:08:57.490 from the appropriate section of the
00:08:59.250 00:08:59.260 turbine flows through the shell side
00:09:02.300 00:09:02.310 because the steam doesn't come in
00:09:04.590 00:09:04.600 contact with the condensate or feed
00:09:06.570 00:09:06.580 water in the heater the heater is called
00:09:09.300 00:09:09.310 a closed heater some plants have
00:09:13.080 00:09:13.090 parallel trains or strings of heaters
00:09:15.630 00:09:15.640 with several heaters in each train all
00:09:18.990 00:09:19.000 the heaters use extraction steam from
00:09:21.420 00:09:21.430 the turbine to heat condensate or feed
00:09:23.640 00:09:23.650 water typically to recover the maximum
00:09:28.560 00:09:28.570 amount of heat from the extraction steam
00:09:30.690 00:09:30.700 a train of heaters uses a cascading
00:09:34.080 00:09:34.090 drain system in each heater in the Train
00:09:37.710 00:09:37.720 drips are sub cooled by the transfer of
00:09:40.350 00:09:40.360 heat to the feed water in the heaters
00:09:42.750 00:09:42.760 drain cooler section this helps keep the
00:09:45.600 00:09:45.610 drips from flashing to steam in the
00:09:47.850 00:09:47.860 drain line the flow of drips moves from
00:09:51.120 00:09:51.130 the highest pressure heater to the lower
00:09:53.280 00:09:53.290 pressure heaters that is the drips flow
00:09:57.030 00:09:57.040 through the normal drain line from one
00:09:59.130 00:09:59.140 heater into the shell side of the next
00:10:01.710 00:10:01.720 heater in the Train this heater has a
00:10:04.500 00:10:04.510 lower temperature and a lower shell side
00:10:07.110 00:10:07.120 pressure than the first heater has the
00:10:10.770 00:10:10.780 drips flash to steam because of the
00:10:13.290 00:10:13.300 lower pressure within the heater shell
00:10:15.470 00:10:15.480 the drips also mix with the extraction
00:10:18.510 00:10:18.520 steam that's already in the shell thus
00:10:21.540 00:10:21.550 the drips are another source of heat to
00:10:24.150 00:10:24.160 be transferred to the feed water in the
00:10:26.100 00:10:26.110 tube side of the heater in our example
00:10:29.790 00:10:29.800 the flashing and condensing process for
00:10:32.610 00:10:32.620 the drips continues through the Train of
00:10:35.040 00:10:35.050 heaters until the drips from the heater
00:10:37.470 00:10:37.480 that has the lowest shell temperature
00:10:39.480 00:10:39.490 and pressure flow into the deaerator
00:10:42.000 00:10:42.010 and become part of the feed water in
00:10:45.000 00:10:45.010 other cases such as in the operation of
00:10:47.460 00:10:47.470 low pressure heaters the drips from the
00:10:50.130 00:10:50.140 heater with the lowest pressure and
00:10:51.840 00:10:51.850 temperature flow into the main condenser
00:10:56.510 00:10:56.520 the deaerator heats condensate and also
00:11:00.660 00:11:00.670 helps remove air and non condensable
00:11:02.850 00:11:02.860 gases that can cause corrosion as this
00:11:06.900 00:11:06.910 cutaway
00:11:07.620 00:11:07.630 raishin shows unlike a shell and tube
00:11:10.470 00:11:10.480 heat exchanger the deaerator is an open
00:11:14.040 00:11:14.050 or direct contact heater that is
00:11:17.120 00:11:17.130 condensate is heated when extraction
00:11:19.920 00:11:19.930 steam and condensate contact each other
00:11:22.350 00:11:22.360 and mix in the deaerator as heat is
00:11:26.370 00:11:26.380 transferred from the steam to the
00:11:27.960 00:11:27.970 condensate some of the steam condenses
00:11:30.630 00:11:30.640 and some of the condensate is heated
00:11:33.470 00:11:33.480 this action strips or removes air and
00:11:37.140 00:11:37.150 other non condensable gases from the
00:11:39.150 00:11:39.160 condensate the heated and deaerated
00:11:43.050 00:11:43.060 condensate that collects in the bottom
00:11:45.240 00:11:45.250 of the heater is actually a mixture of
00:11:47.760 00:11:47.770 condensate and drips from the heater
00:11:50.210 00:11:50.220 from the deaerator the liquid will go to
00:11:53.550 00:11:53.560 the hot surge tank for storage from
00:11:56.610 00:11:56.620 there it will go on through the
00:11:58.200 00:11:58.210 condensate and feed water system to the
00:12:00.630 00:12:00.640 boiler air and non condensable gases
00:12:04.830 00:12:04.840 that are removed from the condensate
00:12:07.080 00:12:07.090 flow out of the deaerator through a vent
00:12:10.070 00:12:10.080 the vent may vent directly to the
00:12:13.140 00:12:13.150 atmosphere or it may connect to the main
00:12:15.960 00:12:15.970 condenser or to a vent condenser the hot
00:12:20.550 00:12:20.560 surge tank which may also be called a
00:12:23.340 00:12:23.350 feed water storage tank or a deaerator
00:12:26.160 00:12:26.170 storage tank receives the condensate
00:12:29.100 00:12:29.110 from the bottom of the deaerator the
00:12:33.930 00:12:33.940 level of condensate or water in the tank
00:12:36.390 00:12:36.400 supplies net positive suction head for
00:12:39.900 00:12:39.910 pumps that have their suction piping
00:12:41.940 00:12:41.950 connected to the tank the correct net
00:12:45.030 00:12:45.040 positive suction head is essential to
00:12:47.820 00:12:47.830 keep the pumps from being damaged during
00:12:49.770 00:12:49.780 operation also the volume of water
00:12:53.550 00:12:53.560 called the surge volume contained in the
00:12:56.670 00:12:56.680 tank is used to meet changes in demand
00:12:59.280 00:12:59.290 during operation of the condensate and
00:13:01.290 00:13:01.300 feed water system for example if boiler
00:13:05.700 00:13:05.710 demand increases the boiler feed pumps
00:13:08.760 00:13:08.770 begin pumping feed water from the
00:13:10.800 00:13:10.810 storage tank at a rate that's greater
00:13:13.200 00:13:13.210 than the rate at which condensate is
00:13:15.210 00:13:15.220 being fed to the tank by the condensate
00:13:17.640 00:13:17.650 system the hot surge tank
00:13:21.090 00:13:21.100 supplies enough feed water to meet the
00:13:23.340 00:13:23.350 increased demand for the short time it
00:13:25.680 00:13:25.690 takes for the condensate flow and the
00:13:28.080 00:13:28.090 feed water flow to become equal again
00:13:31.250 00:13:31.260 both deaerators and hot surge tanks
00:13:34.590 00:13:34.600 often have additional connections
00:13:37.310 00:13:37.320 examples are connections from the higher
00:13:39.990 00:13:40.000 pressure feedwater heaters cascading
00:13:42.420 00:13:42.430 drain system and connections to the vent
00:13:45.360 00:13:45.370 system from the high pressure heaters
00:13:50.810 00:13:50.820 proper boiler operation requires the
00:13:54.030 00:13:54.040 flow of feed water into the boiler to
00:13:56.760 00:13:56.770 equal the flow of steam leaving the
00:13:59.100 00:13:59.110 boiler if too much feed water flows into
00:14:02.760 00:14:02.770 the boiler moisture could eventually
00:14:05.040 00:14:05.050 build up and carry over into the main
00:14:07.680 00:14:07.690 steam system on the other hand if
00:14:11.010 00:14:11.020 there's not enough feed water flow to
00:14:13.290 00:14:13.300 meet the demands of the boiler the
00:14:15.210 00:14:15.220 boiler could boil dry feed water flow
00:14:19.290 00:14:19.300 can be controlled in various ways a feed
00:14:22.410 00:14:22.420 water regulating valve may be used or as
00:14:25.530 00:14:25.540 in this system feed water flow can be
00:14:28.350 00:14:28.360 controlled simply by varying the speed
00:14:31.020 00:14:31.030 of the boiler feedwater pumps other
00:14:33.840 00:14:33.850 systems control feed water flow by using
00:14:36.630 00:14:36.640 a combination of varying the speed of
00:14:39.330 00:14:39.340 the boiler feedwater pumps and changing
00:14:42.090 00:14:42.100 the position of a feed water regulating
00:14:44.220 00:14:44.230 valve two additional systems are
00:14:49.950 00:14:49.960 normally associated with a condensate in
00:14:52.260 00:14:52.270 feed water system they are a chemical
00:14:55.560 00:14:55.570 addition system and a make up water
00:14:58.830 00:14:58.840 system the chemical addition system may
00:15:02.760 00:15:02.770 be connected to the condensate system
00:15:04.950 00:15:04.960 the feed water system or both it
00:15:08.490 00:15:08.500 generally includes pumps and associated
00:15:11.130 00:15:11.140 equipment for adding chemicals such as
00:15:13.440 00:15:13.450 hydrazine to prevent corrosion and
00:15:15.990 00:15:16.000 ammonia to control pH the make up water
00:15:21.060 00:15:21.070 system is connected to the main
00:15:23.130 00:15:23.140 condensers hot well this system adds
00:15:26.220 00:15:26.230 pure water to the condensate system to
00:15:29.160 00:15:29.170 compensate for water losses that may
00:15:31.200 00:15:31.210 occur due to condensate sampling
00:15:34.300 00:15:34.310 to steam or water leaks in the system
00:15:36.990 00:15:37.000 the makeup water is stored in a
00:15:39.790 00:15:39.800 condensate storage tank makeup water
00:15:43.000 00:15:43.010 system designs vary but most also
00:15:45.910 00:15:45.920 include purifying equipment such as
00:15:48.370 00:15:48.380 evaporators and demineralize errs if
00:15:53.710 00:15:53.720 you're responsible for keeping a
00:15:55.540 00:15:55.550 condensate and feed water system running
00:15:57.820 00:15:57.830 smoothly
00:15:58.420 00:15:58.430 you must be thoroughly familiar with
00:16:00.970 00:16:00.980 normal operating conditions for the
00:16:02.950 00:16:02.960 system so you can distinguish between
00:16:05.010 00:16:05.020 usual and unusual conditions making
00:16:08.920 00:16:08.930 regular checks of levels temperatures
00:16:11.500 00:16:11.510 pressures flows and valve positions
00:16:14.860 00:16:14.870 throughout the system as it operates
00:16:16.560 00:16:16.570 helps you detect problems early so that
00:16:19.840 00:16:19.850 major trouble and costly downtime can be
00:16:22.660 00:16:22.670 prevented specific concerns associated
00:16:25.990 00:16:26.000 with the operation of your facility's
00:16:28.420 00:16:28.430 condensate and feed water system are
00:16:30.910 00:16:30.920 usually covered in your plants standard
00:16:33.190 00:16:33.200 operating procedures and in the
00:16:35.260 00:16:35.270 operating manuals for the individual
00:16:37.329 00:16:37.339 pieces of equipment in this part however
00:16:40.150 00:16:40.160 we'll look at some basic operating
00:16:42.430 00:16:42.440 checks that are common for most
00:16:44.110 00:16:44.120 condensate in feed water systems a
00:16:50.010 00:16:50.020 typical condensate in feed water system
00:16:52.900 00:16:52.910 includes several multistage centrifugal
00:16:55.750 00:16:55.760 pumps checking the pressures
00:16:58.390 00:16:58.400 temperatures and lubrication for the
00:17:00.910 00:17:00.920 pumps during normal operation of the
00:17:02.860 00:17:02.870 system is a routine operator
00:17:05.050 00:17:05.060 responsibility checking pump suction and
00:17:10.120 00:17:10.130 discharge pressures periodically helps
00:17:12.699 00:17:12.709 ensure that each pump is operating
00:17:14.290 00:17:14.300 correctly and that proper flow through
00:17:17.079 00:17:17.089 the system is maintained proper bearing
00:17:20.500 00:17:20.510 lubrication is critical to keep the
00:17:22.689 00:17:22.699 pumps in a condensate and feed water
00:17:24.579 00:17:24.589 system in good working order to make
00:17:27.699 00:17:27.709 sure that a pumps bearings are being
00:17:29.500 00:17:29.510 properly lubricated you should check for
00:17:32.020 00:17:32.030 overheating excessive vibration
00:17:35.370 00:17:35.380 contaminated lubricant and low lubricant
00:17:38.530 00:17:38.540 level one way to check for overheating
00:17:41.980 00:17:41.990 or excessive vibration is by touching
00:17:44.590 00:17:44.600 the bearing housing you can also use an
00:17:48.169 00:17:48.179 instrument called a pyrometer to measure
00:17:50.450 00:17:50.460 the temperature at the bearing housing
00:17:52.460 00:17:52.470 and a vibration meter to measure the
00:17:55.970 00:17:55.980 amount of vibration to check the flow
00:17:59.690 00:17:59.700 level and condition of the lubricant
00:18:01.999 00:18:02.009 sight glasses are commonly used
00:18:04.730 00:18:04.740 if lubricating oil in a sight glass has
00:18:07.759 00:18:07.769 an unusual color this could be a sign
00:18:10.549 00:18:10.559 that the oil has been contaminated and
00:18:12.649 00:18:12.659 should be replaced for this pump a gauge
00:18:16.639 00:18:16.649 measures the temperature of the
00:18:18.409 00:18:18.419 lubricating oil leaving the pumps
00:18:20.180 00:18:20.190 bearings
00:18:20.810 00:18:20.820 if the reading isn't within the normal
00:18:23.330 00:18:23.340 temperature range there's generally a
00:18:25.639 00:18:25.649 problem that should be reported many
00:18:28.850 00:18:28.860 pumps use cooling water to cool the
00:18:31.070 00:18:31.080 pumps bearings when you check these
00:18:33.529 00:18:33.539 pumps make sure that the valves in the
00:18:35.810 00:18:35.820 cooling water lines are open a
00:18:38.710 00:18:38.720 centrifugal pump often uses seal water
00:18:41.899 00:18:41.909 to help keep fluid from leaking out of
00:18:44.149 00:18:44.159 the pump during normal operation you
00:18:47.180 00:18:47.190 should check the seal water to be sure
00:18:49.159 00:18:49.169 it's working properly
00:18:51.999 00:18:52.009 also if funnel drains are used for seal
00:18:55.340 00:18:55.350 water leak off check the drains for
00:18:57.799 00:18:57.809 proper seal water flow if the flow is
00:19:01.070 00:19:01.080 greater than normal this could indicate
00:19:03.049 00:19:03.059 a leaking seal if a pump has a minimum
00:19:08.840 00:19:08.850 flow requirement a flow rate less than
00:19:11.810 00:19:11.820 the minimum causes higher turbulence and
00:19:14.299 00:19:14.309 greater friction which generates heat in
00:19:16.909 00:19:16.919 the pump so recirculation lines and
00:19:20.180 00:19:20.190 valves are used to maintain minimum flow
00:19:23.029 00:19:23.039 and prevent overheating if flow through
00:19:26.840 00:19:26.850 the pump goes below the minimum flow
00:19:28.940 00:19:28.950 requirement the valves in the
00:19:30.980 00:19:30.990 recirculation line are opened to
00:19:33.320 00:19:33.330 maintain minimum flow but when flow
00:19:36.230 00:19:36.240 through the pump is above the minimum
00:19:38.090 00:19:38.100 level the valves in the recirculation
00:19:40.430 00:19:40.440 line should be closed condensate pumps
00:19:44.930 00:19:44.940 usually have suction and discharge vent
00:19:47.629 00:19:47.639 lines that are connected to the main
00:19:49.639 00:19:49.649 condenser in most cases the valve in the
00:19:53.419 00:19:53.429 discharge vent line is closed after the
00:19:56.389 00:19:56.399 condensate pump has been started and is
00:19:58.759 00:19:58.769 operating normally
00:20:02.430 00:20:02.440 allô hot well level occurs when the
00:20:05.529 00:20:05.539 amount of condensate leaving the main
00:20:07.509 00:20:07.519 condenser is greater than the amount of
00:20:10.299 00:20:10.309 steam that's condensing this condition
00:20:13.570 00:20:13.580 could cause the condensate pumps to lose
00:20:15.759 00:20:15.769 their prime a high hot well level occurs
00:20:19.779 00:20:19.789 when the amount of steam condensed in
00:20:22.330 00:20:22.340 the main condenser is greater than the
00:20:24.789 00:20:24.799 amount of condensate removed by the
00:20:26.919 00:20:26.929 condensate pumps this condition could
00:20:30.369 00:20:30.379 flood the lower sections of the tubes in
00:20:32.619 00:20:32.629 the main condenser and reduce the
00:20:34.899 00:20:34.909 condensers overall condensing ability in
00:20:38.200 00:20:38.210 an extreme case water from the main
00:20:40.690 00:20:40.700 condenser could get up into the turbine
00:20:43.210 00:20:43.220 and destroy it's moving blades a level
00:20:47.080 00:20:47.090 control loop is used to maintain the
00:20:49.239 00:20:49.249 correct level of condensate in the hot
00:20:51.430 00:20:51.440 well basically condensate flow out of
00:20:55.060 00:20:55.070 the hot well is decreased if the level
00:20:57.789 00:20:57.799 falls below a preset minimum and
00:21:00.269 00:21:00.279 increased if the level exceeds a preset
00:21:03.580 00:21:03.590 maximum a typical condensate in feed
00:21:09.669 00:21:09.679 water system has several shell and tube
00:21:12.190 00:21:12.200 heat exchangers or closed heaters some
00:21:15.789 00:21:15.799 may be used as condensers but most are
00:21:18.580 00:21:18.590 used as low intermediate or high
00:21:20.619 00:21:20.629 pressure heaters for the condensate in
00:21:22.989 00:21:22.999 feed water the levels temperatures and
00:21:26.830 00:21:26.840 pressures for all the closed heaters
00:21:29.080 00:21:29.090 should be checked periodically during
00:21:31.149 00:21:31.159 normal system operation to make sure
00:21:33.789 00:21:33.799 that these operating variables remain
00:21:36.310 00:21:36.320 within predetermined normal ranges we'll
00:21:40.450 00:21:40.460 look at some operating checks for a high
00:21:42.669 00:21:42.679 pressure closed feed water heater most
00:21:45.820 00:21:45.830 of the checks for this type of heater
00:21:47.529 00:21:47.539 also apply to low and intermediate
00:21:50.259 00:21:50.269 pressure condensate or feed water
00:21:52.060 00:21:52.070 heaters to monitor the level in the
00:21:55.480 00:21:55.490 shell side of the heater you can usually
00:21:58.029 00:21:58.039 check a sight glass on the heater an
00:22:00.779 00:22:00.789 abnormal level in the sight glass could
00:22:03.580 00:22:03.590 indicate a problem that should be
00:22:05.049 00:22:05.059 reported temperature gauges indicate the
00:22:09.789 00:22:09.799 temperature of the feed water leaving
00:22:11.769 00:22:11.779 the heater and the temperature of the
00:22:14.169 00:22:14.179 extract
00:22:14.770 00:22:14.780 steam entering the heater for proper
00:22:18.040 00:22:18.050 system performance and the overall
00:22:19.810 00:22:19.820 efficiency of the plant it's very
00:22:22.150 00:22:22.160 important that these temperatures stay
00:22:24.460 00:22:24.470 within their normal operating ranges
00:22:26.940 00:22:26.950 pressure gauges are used to monitor the
00:22:29.770 00:22:29.780 pressure of the extraction steam that
00:22:32.110 00:22:32.120 enters the heater and the feed water
00:22:34.420 00:22:34.430 that passes through the heater the
00:22:36.330 00:22:36.340 reading for the extraction steam
00:22:38.650 00:22:38.660 pressure normally varies with turbine
00:22:41.170 00:22:41.180 load the greater the turbine load the
00:22:43.960 00:22:43.970 higher the extraction steam pressure
00:22:46.830 00:22:46.840 feed water heaters and many condensate
00:22:49.720 00:22:49.730 and feed water systems are installed in
00:22:52.270 00:22:52.280 trains or strings that are monitored as
00:22:55.090 00:22:55.100 a unit during normal operation of the
00:22:57.250 00:22:57.260 system in this arrangement the final
00:23:00.520 00:23:00.530 feed water outlet temperature is
00:23:02.740 00:23:02.750 commonly used as one way to monitor the
00:23:05.470 00:23:05.480 performance of the heaters the final
00:23:08.800 00:23:08.810 feed water outlet temperature is the
00:23:11.200 00:23:11.210 temperature of the feed water coming out
00:23:13.240 00:23:13.250 of the highest pressure feed water
00:23:15.130 00:23:15.140 heater on its way to the boilers
00:23:17.170 00:23:17.180 economizer checking this temperature is
00:23:20.350 00:23:20.360 the quickest way to get an overall
00:23:22.240 00:23:22.250 picture of how well the feed water
00:23:24.250 00:23:24.260 heaters are doing their job if the final
00:23:27.940 00:23:27.950 feed water outlet temperature is at the
00:23:30.400 00:23:30.410 expected level for the given load then
00:23:33.010 00:23:33.020 each of the feed water heaters in the
00:23:34.930 00:23:34.940 Train is probably transferring heat at
00:23:37.690 00:23:37.700 the proper rate but sometimes a heater
00:23:41.230 00:23:41.240 within the Train may be transferring
00:23:43.510 00:23:43.520 heat at an improper rate even though the
00:23:46.510 00:23:46.520 final feed water outlet temperature is
00:23:48.790 00:23:48.800 at the expected level so periodically
00:23:51.640 00:23:51.650 you should also check the outlet
00:23:53.980 00:23:53.990 temperature of each heater in the Train
00:23:56.020 00:23:56.030 the deaerator
00:23:59.620 00:23:59.630 which is an open heater and the hot
00:24:02.350 00:24:02.360 surge or deaerator storage tank that's
00:24:05.080 00:24:05.090 associated with the deaerator must also
00:24:07.810 00:24:07.820 be monitored when a condensate and feed
00:24:10.150 00:24:10.160 water system is in operation check the
00:24:13.420 00:24:13.430 level of water in the hot surge tank
00:24:15.570 00:24:15.580 there's usually a level sight glass on
00:24:18.550 00:24:18.560 the tank that's used for this purpose if
00:24:21.730 00:24:21.740 the level is too high water could flow
00:24:24.280 00:24:24.290 into the deaerator and in extreme cases
00:24:26.970 00:24:26.980 even into
00:24:28.240 00:24:28.250 the extraction system piping if the
00:24:31.570 00:24:31.580 level is too low the net positive
00:24:33.880 00:24:33.890 suction head for the pumps downstream of
00:24:36.550 00:24:36.560 the tank is reduced as a result the
00:24:39.670 00:24:39.680 pumps could be damaged monitoring the
00:24:43.270 00:24:43.280 performance of the D aerator is
00:24:45.300 00:24:45.310 important for maintaining overall system
00:24:48.280 00:24:48.290 and plant efficiency check the
00:24:51.010 00:24:51.020 appropriate gauges for the proper
00:24:52.960 00:24:52.970 extraction steam temperature and
00:24:54.730 00:24:54.740 pressure look for any signs of leakage
00:24:58.480 00:24:58.490 and make sure that all the valves for
00:25:01.330 00:25:01.340 the deaerator are in the proper
00:25:03.160 00:25:03.170 positions
00:25:04.410 00:25:04.420 watch for excess venting from the
00:25:07.120 00:25:07.130 deaerator that can cause a major loss of
00:25:10.060 00:25:10.070 heat energy and fluid from the deaerator
00:25:12.340 00:25:12.350 which will decrease plant efficiency
00:25:15.300 00:25:15.310 also watch for insufficient venting that
00:25:19.090 00:25:19.100 will allow oxygen and other gases to
00:25:21.460 00:25:21.470 remain in the condensate and feed water
00:25:23.350 00:25:23.360 system and cause problems downstream
00:25:28.290 00:25:28.300 problems can occur with any of the
00:25:30.790 00:25:30.800 components in a condensate in feed water
00:25:33.010 00:25:33.020 system including the pumps heaters
00:25:35.830 00:25:35.840 storage tanks and their auxiliaries such
00:25:39.340 00:25:39.350 as valves vents motors couplings and
00:25:42.700 00:25:42.710 piping in this part we'll look at
00:25:46.030 00:25:46.040 typical examples of dealing with some
00:25:48.100 00:25:48.110 operating problems that are common in
00:25:50.410 00:25:50.420 most condensate and feed water systems
00:25:52.540 00:25:52.550 but keep in mind that you'll need to
00:25:55.240 00:25:55.250 review your plants standard operating
00:25:57.580 00:25:57.590 procedures to learn the exact steps to
00:26:00.370 00:26:00.380 follow in your facility many operating
00:26:03.910 00:26:03.920 problems in a condensate and feed water
00:26:06.160 00:26:06.170 system are relatively simple to correct
00:26:09.000 00:26:09.010 however a problem in one component
00:26:12.210 00:26:12.220 usually affects the operation of other
00:26:14.860 00:26:14.870 components in the system as well
00:26:17.100 00:26:17.110 consequently some operating problems can
00:26:20.410 00:26:20.420 require considerable troubleshooting
00:26:22.450 00:26:22.460 skills
00:26:25.290 00:26:25.300 several heaters are included in a
00:26:27.730 00:26:27.740 condensate in feed water system so
00:26:30.250 00:26:30.260 heater problems are a typical operating
00:26:32.920 00:26:32.930 concern we'll look at some problems in a
00:26:35.950 00:26:35.960 closed high-pressure feed water heater
00:26:39.690 00:26:39.700 improper venting of the heater
00:26:42.040 00:26:42.050 can cause air binding when this occurs
00:26:45.040 00:26:45.050 air is trapped in either the tube side
00:26:47.770 00:26:47.780 or the shell side of the heater air that
00:26:51.520 00:26:51.530 collects in the waterboxxes on the tube
00:26:53.590 00:26:53.600 side of the heater can restrict the flow
00:26:56.170 00:26:56.180 of water through some of the tubes the
00:26:58.960 00:26:58.970 restricted flow causes the velocity of
00:27:01.690 00:27:01.700 the feed water to increase because the
00:27:04.600 00:27:04.610 same amount of water must go through
00:27:06.400 00:27:06.410 fewer tubes the increased feed water
00:27:10.030 00:27:10.040 velocity can cause the terminal
00:27:12.430 00:27:12.440 temperature difference or TTD to
00:27:15.310 00:27:15.320 increase although the drain cooler
00:27:17.980 00:27:17.990 approach or DCA remains normal another
00:27:23.230 00:27:23.240 indication of air binding in the
00:27:24.940 00:27:24.950 waterboxxes is an increase in the
00:27:27.580 00:27:27.590 differential pressure or Delta P across
00:27:30.580 00:27:30.590 the heater if air binding is indicated
00:27:33.940 00:27:33.950 by either an increased TTD or an
00:27:36.850 00:27:36.860 increased Delta P venting the air from
00:27:39.790 00:27:39.800 the water boxes should return the feed
00:27:42.010 00:27:42.020 water flow and pressure to normal air
00:27:45.160 00:27:45.170 binding also occurs if air and gases
00:27:48.340 00:27:48.350 collect on the shell side of the heater
00:27:50.310 00:27:50.320 the increasing volume of air blankets
00:27:53.770 00:27:53.780 the tubes and prevent steam from
00:27:55.960 00:27:55.970 contacting them this in turn reduces the
00:27:59.290 00:27:59.300 amount of heat transferred by the heater
00:28:01.210 00:28:01.220 as a result the feed water outlet
00:28:04.960 00:28:04.970 temperature decreases the TT D however
00:28:08.940 00:28:08.950 increases because the extraction steam
00:28:12.070 00:28:12.080 temperature remains the same even though
00:28:14.860 00:28:14.870 the feed water outlet temperature has
00:28:16.870 00:28:16.880 gone down the efficiency of the drain
00:28:20.050 00:28:20.060 cooler isn't affected so the dca remains
00:28:23.470 00:28:23.480 normal you can usually correct the
00:28:26.800 00:28:26.810 problem of air binding on the shell side
00:28:28.660 00:28:28.670 of a heater by venting the shell side to
00:28:31.750 00:28:31.760 remove the air the TT D should then
00:28:34.690 00:28:34.700 return to normal as a result of the
00:28:39.070 00:28:39.080 restricted heat transfer caused by a
00:28:41.170 00:28:41.180 high heater level the TT D increases the
00:28:45.550 00:28:45.560 dca however usually remains normal
00:28:48.340 00:28:48.350 because the flow of drips through the
00:28:50.620 00:28:50.630 drain cooler may not change or it may be
00:28:53.500 00:28:53.510 less than normal
00:28:55.720 00:28:55.730 to determine whether an increased TTD is
00:28:58.150 00:28:58.160 caused by air binding or by a high-level
00:29:00.900 00:29:00.910 check the sight glass for the shell side
00:29:03.640 00:29:03.650 of the heater if the level in the sight
00:29:06.190 00:29:06.200 glass is high then the problem is most
00:29:09.040 00:29:09.050 likely caused by an abnormal level not
00:29:11.830 00:29:11.840 by air binding if a heaters level is too
00:29:18.310 00:29:18.320 low steam is able to blow through the
00:29:21.100 00:29:21.110 heater and out the drain in turn the
00:29:24.160 00:29:24.170 flow of extraction steam increases and
00:29:26.680 00:29:26.690 this can cause erosion inside the heater
00:29:29.320 00:29:29.330 and eventually tube failure because the
00:29:33.310 00:29:33.320 low level allows steam to flow through
00:29:35.470 00:29:35.480 the heaters drain cooler without
00:29:36.940 00:29:36.950 condensing a low level causes the dca to
00:29:41.050 00:29:41.060 increase drastically
00:29:42.820 00:29:42.830 while the TTD typically remains at or
00:29:45.910 00:29:45.920 near normal tube leaks are another
00:29:50.440 00:29:50.450 common operating problem associated with
00:29:53.080 00:29:53.090 closed heaters like this high-pressure
00:29:55.300 00:29:55.310 feed water heater even small leaks can
00:29:58.960 00:29:58.970 significantly increase the volume of
00:30:01.090 00:30:01.100 water in the drips causing the lower
00:30:03.550 00:30:03.560 tubes in the heater to be blanketed with
00:30:05.740 00:30:05.750 feed water tube leaks also make the
00:30:08.980 00:30:08.990 heaters level control valve open farther
00:30:11.470 00:30:11.480 than normal as a tube leak becomes
00:30:14.830 00:30:14.840 larger the volume of water flowing into
00:30:17.710 00:30:17.720 the shell side of the heater can exceed
00:30:20.200 00:30:20.210 the level control valves capacity then
00:30:23.410 00:30:23.420 the emergency drain valve must be used
00:30:25.780 00:30:25.790 to control the level in the heater a
00:30:28.380 00:30:28.390 large tube leak is a serious problem
00:30:31.180 00:30:31.190 that calls for immediate attention
00:30:33.360 00:30:33.370 because it can allow water to enter the
00:30:36.310 00:30:36.320 turbine to prevent damaging or
00:30:38.950 00:30:38.960 destroying the turbine you should
00:30:40.930 00:30:40.940 isolate and bypass the heater as soon as
00:30:43.750 00:30:43.760 possible of course operating with even a
00:30:47.560 00:30:47.570 relatively small tube leak is
00:30:49.390 00:30:49.400 inefficient so it's important to find
00:30:52.450 00:30:52.460 small leaks early and get them corrected
00:30:55.110 00:30:55.120 small tube leaks may be difficult to
00:30:57.730 00:30:57.740 detect though because they don't show up
00:31:00.220 00:31:00.230 on instrumentation but some small leaks
00:31:03.670 00:31:03.680 may become noticeable when you calculate
00:31:05.980 00:31:05.990 the TTD and the dca for a heat
00:31:10.450 00:31:10.460 in many cases operators must determine
00:31:14.060 00:31:14.070 exactly which heater in a train is not
00:31:16.610 00:31:16.620 operating properly in this example one
00:31:20.210 00:31:20.220 heater in a train of high-pressure
00:31:21.919 00:31:21.929 feedwater heaters is malfunctioning as a
00:31:25.340 00:31:25.350 result there's an increase in the
00:31:27.769 00:31:27.779 temperature difference or delta T across
00:31:30.440 00:31:30.450 the higher pressure heaters downstream
00:31:33.080 00:31:33.090 from the malfunctioning one the
00:31:36.200 00:31:36.210 increased delta T causes more heat to be
00:31:39.470 00:31:39.480 transferred in the downstream heaters
00:31:41.499 00:31:41.509 making up some of the difference caused
00:31:44.060 00:31:44.070 by the heater that's not operating
00:31:45.980 00:31:45.990 properly to locate the heater that's not
00:31:49.369 00:31:49.379 operating properly you should generally
00:31:52.190 00:31:52.200 start by checking the final feed water
00:31:54.769 00:31:54.779 outlet temperature to see if that value
00:31:57.560 00:31:57.570 is within the normal range then work
00:32:00.529 00:32:00.539 backwards noting the heater outlet
00:32:03.019 00:32:03.029 temperature for each heater in the Train
00:32:04.970 00:32:04.980 if the difference between the actual
00:32:07.610 00:32:07.620 reading and the expected one becomes
00:32:10.610 00:32:10.620 greater with each heater there's a
00:32:12.769 00:32:12.779 malfunctioning heater upstream to
00:32:16.310 00:32:16.320 pinpoint the exact heater that's causing
00:32:18.350 00:32:18.360 the problem follow a step-by-step
00:32:20.950 00:32:20.960 troubleshooting procedure which includes
00:32:23.869 00:32:23.879 checking the temperature rise across
00:32:25.909 00:32:25.919 each heater calculating their T TDs and
00:32:29.210 00:32:29.220 DCA's and checking the positions of
00:32:32.240 00:32:32.250 their normal drain valves then comparing
00:32:35.659 00:32:35.669 the actual conditions with the expected
00:32:38.389 00:32:38.399 normal conditions for the heaters at the
00:32:40.549 00:32:40.559 given load a typical condensate in feed
00:32:47.480 00:32:47.490 water system also has several pumps so
00:32:50.990 00:32:51.000 operating problems often involve
00:32:53.090 00:32:53.100 troubleshooting pump malfunctions
00:32:55.480 00:32:55.490 for example this operator notices that
00:32:59.570 00:32:59.580 although this boiler feed pump is
00:33:01.460 00:33:01.470 operating at top speed the flow of feed
00:33:04.490 00:33:04.500 water to the boiler is inadequate to
00:33:08.090 00:33:08.100 keep the situation from getting worse
00:33:10.009 00:33:10.019 a second boiler feed pump is brought
00:33:12.649 00:33:12.659 online
00:33:13.240 00:33:13.250 this increases the feed water flow to an
00:33:16.549 00:33:16.559 adequate rate to keep the boiler
00:33:18.500 00:33:18.510 operating properly then company
00:33:21.560 00:33:21.570 procedures are follow
00:33:22.850 00:33:22.860 to analyze and correct the problem
00:33:25.780 00:33:25.790 detailed troubleshooting could determine
00:33:28.580 00:33:28.590 that the inadequate feed water flow was
00:33:31.160 00:33:31.170 caused by an operating problem in the
00:33:33.440 00:33:33.450 first boiler feed pump on the other hand
00:33:36.530 00:33:36.540 further analysis could show that the
00:33:38.990 00:33:39.000 pump is working properly and a
00:33:41.090 00:33:41.100 malfunction elsewhere in the condensate
00:33:43.220 00:33:43.230 in feed water system could be the cause
00:33:45.380 00:33:45.390 of the inadequate feed water flow
Office location
Engineering company LOTUS®
Russia, Ekaterinburg, Lunacharskogo street, 240/12

Phone: +7 343 216 77 75

E-mail: info@lotus1.ru

Sales phone

Russia: +7 343 216 77 75

WhatsApp: +79122710308