Dustcheck's Non-Delta P (Standard Sequence) Controller - Dust Extraction Unit

WEBVTT
Kind: captions
Language: en

00:00:00.030
this film shows how to set up the
00:00:02.030 00:00:02.040 various parameters on a dust check
00:00:03.980 00:00:03.990 sequence controller without a delta P
00:00:06.650 00:00:06.660 control facility to establish if you
00:00:09.320 00:00:09.330 have a delta P controller look for two
00:00:11.839 00:00:11.849 pneumatic connections on the side of the
00:00:13.850 00:00:13.860 controller connected internally with
00:00:15.980 00:00:15.990 plastic type if your controller does
00:00:18.410 00:00:18.420 have these then you have a delta P
00:00:20.510 00:00:20.520 controller and this video is not
00:00:22.519 00:00:22.529 applicable instead please view our Delta
00:00:25.490 00:00:25.500 P controller film the controller has
00:00:28.099 00:00:28.109 eight functions seven of which can be
00:00:30.500 00:00:30.510 set by the user
00:00:31.959 00:00:31.969 controllers supplied with dust filters
00:00:34.520 00:00:34.530 are factory preset for the unit supplied
00:00:37.069 00:00:37.079 changes are not normally required
00:00:39.319 00:00:39.329 however there may be an instance where
00:00:41.900 00:00:41.910 the process allows a change or the
00:00:44.090 00:00:44.100 controller has been supplied as a
00:00:45.799 00:00:45.809 replacement the controller has a keypad
00:00:48.470 00:00:48.480 consisting of keys a B and C and a
00:00:51.709 00:00:51.719 three-digit display which are used in
00:00:54.139 00:00:54.149 conjunction with each other to access
00:00:56.209 00:00:56.219 view adjust and store the controller
00:00:58.700 00:00:58.710 settings you access the settings menu by
00:01:01.610 00:01:01.620 pressing key C pressing C again Scrolls
00:01:04.910 00:01:04.920 through the available functions the
00:01:07.070 00:01:07.080 functions are labeled as F 0 1 f 0 2 etc
00:01:10.969 00:01:10.979 and their purpose is listed in the
00:01:13.429 00:01:13.439 instruction leaflet enclosed with the
00:01:15.770 00:01:15.780 controller once the desired selection is
00:01:18.499 00:01:18.509 displayed press a to view the current
00:01:20.870 00:01:20.880 setting and make any changes use keys a
00:01:24.109 00:01:24.119 and C to adjust the setting up or down
00:01:26.899 00:01:26.909 once the value required is displayed
00:01:29.270 00:01:29.280 press B to store the value if you have
00:01:32.330 00:01:32.340 completed all the changes pressing B
00:01:34.730 00:01:34.740 again puts the controller into operating
00:01:37.190 00:01:37.200 mode to make further changes to the
00:01:39.499 00:01:39.509 other settings press C until the desired
00:01:42.140 00:01:42.150 function is displayed and a to start
00:01:44.660 00:01:44.670 changes please be aware the controller
00:01:47.210 00:01:47.220 will revert to operating mode after 5
00:01:49.850 00:01:49.860 minutes of inactivity on the keypad
00:01:51.770 00:01:51.780 let's now go through each function and
00:01:54.260 00:01:54.270 setting in turn since the controller
00:01:57.080 00:01:57.090 requires a power supply during the
00:01:59.090 00:01:59.100 setting operation extreme care should be
00:02:01.399 00:02:01.409 taken to avoid contact with live
00:02:03.590 00:02:03.600 terminals function f 0 1 is to allow the
00:02:07.370 00:02:07.380 controller to stop and start by an
00:02:09.589 00:02:09.599 external signal using terminals 12 and
00:02:12.110 00:02:12.120 13 or 14
00:02:13.600 00:02:13.610 fifteen or all for the normal factory
00:02:16.840 00:02:16.850 setting is one which ignores any
00:02:19.150 00:02:19.160 external signal setting to zero allows
00:02:22.030 00:02:22.040 their signal to be used press C to get
00:02:24.910 00:02:24.920 the F zero one menu if you have just
00:02:28.090 00:02:28.100 entered the menu it should show F zero
00:02:30.310 00:02:30.320 one
00:02:30.850 00:02:30.860 if not press C again to scroll through
00:02:33.130 00:02:33.140 until you have F zero one showing on the
00:02:35.920 00:02:35.930 display use keys a and C to change the
00:02:39.100 00:02:39.110 setting once correct press B to store
00:02:42.310 00:02:42.320 the setting
00:02:46.220 00:02:46.230 f02 sets the period in seconds for the
00:02:49.680 00:02:49.690 duration of the valve opening for most
00:02:52.170 00:02:52.180 dust filters this is set to 0.1 f03 sets
00:02:57.150 00:02:57.160 the time interval between firing the
00:02:59.070 00:02:59.080 solenoids and is often set to 15 seconds
00:03:02.390 00:03:02.400 f-zero 4 is set to the number of
00:03:05.160 00:03:05.170 solenoid valves to be activated it
00:03:07.440 00:03:07.450 allows any number up to the maximum the
00:03:09.930 00:03:09.940 controller can handle f05
00:03:12.630 00:03:12.640 provides the facility to have the
00:03:14.430 00:03:14.440 controller run through a series of
00:03:16.080 00:03:16.090 cleaning cycles after the air mover has
00:03:18.240 00:03:18.250 stopped and no air flow exists through
00:03:20.729 00:03:20.739 the filter unit if this facility is
00:03:22.949 00:03:22.959 required function f01 should also be set
00:03:26.340 00:03:26.350 to zero and a connection is required on
00:03:28.530 00:03:28.540 terminals 12 and 13 to provide the
00:03:31.170 00:03:31.180 signal f06 is used for testing and
00:03:34.400 00:03:34.410 diagnostics and has no setting facility
00:03:37.259 00:03:37.269 it allows you to select a particular
00:03:39.180 00:03:39.190 valve and force it to activate when f06
00:03:43.350 00:03:43.360 is displayed press C to select the valve
00:03:45.990 00:03:46.000 to be activated then press a to activate
00:03:49.940 00:03:49.950 f07 defines the type of signal that will
00:03:53.220 00:03:53.230 be used to provide the external signal
00:03:55.500 00:03:55.510 to stop and start the controller if this
00:03:58.530 00:03:58.540 facility is required function f0 one
00:04:01.470 00:04:01.480 should also be set to zero and a
00:04:03.660 00:04:03.670 connection is required on terminals 14
00:04:05.880 00:04:05.890 and 15 to provide the signal setting
00:04:08.940 00:04:08.950 this to zero allows the signal to be
00:04:11.190 00:04:11.200 provided by a pressure switch setting it
00:04:13.590 00:04:13.600 to one for a normal open and closed
00:04:15.960 00:04:15.970 signal say from a PLC finally f08 which
00:04:21.150 00:04:21.160 allows the output voltage to be selected
00:04:23.460 00:04:23.470 this should be set to the input voltage
00:04:25.560 00:04:25.570 of the solenoid valve normally 24 volts
00:04:29.270 00:04:29.280 for further information on any of dose
00:04:32.219 00:04:32.229 checks products please get in touch