HES Scheme training - boilers installed not to required standard

WEBVTT
Kind: captions
Language: en

00:00:03.320
[Music]
00:00:07.210 00:00:07.220 hi I'm Colin Donnelly I work with Riga
00:00:10.490 00:00:10.500 on behalf of the sustainable energy
00:00:12.230 00:00:12.240 authority of Ireland on the home energy
00:00:14.629 00:00:14.639 saving scheme today I'm going to be
00:00:16.460 00:00:16.470 talking you through an example of two
00:00:18.230 00:00:18.240 inspections that have boiler and heating
00:00:20.330 00:00:20.340 control work carried out the first step
00:00:31.700 00:00:31.710 is to go to the seven-day 24 hour time
00:00:34.100 00:00:34.110 clock and turn on the hot water only
00:00:36.049 00:00:36.059 setting this gives us a few minutes to
00:00:38.450 00:00:38.460 look at the rest of the installation who
00:00:40.310 00:00:40.320 are waiting for the hot water to heat up
00:00:41.889 00:00:41.899 here we have a condensing oil boiler
00:00:44.630 00:00:44.640 there are a number of points there at a
00:00:46.160 00:00:46.170 glance we can see that aren't up to the
00:00:48.200 00:00:48.210 standard of the scheme
00:00:51.220 00:00:51.230 here we can see that the condensate pipe
00:00:53.830 00:00:53.840 is not liked externally even though it
00:00:55.900 00:00:55.910 falls immediately when it exits the
00:00:57.610 00:00:57.620 boiler casing it is important to this as
00:01:00.100 00:01:00.110 well insulation stopped at freezing
00:01:01.540 00:01:01.550 during cold weather in this clip you
00:01:05.079 00:01:05.089 will notice that the safety blow-off
00:01:06.370 00:01:06.380 valve is terminating horizontally this
00:01:09.370 00:01:09.380 is not to the standard of the home
00:01:10.690 00:01:10.700 energy saving scheme this should be
00:01:12.910 00:01:12.920 pointing down and terminating 100
00:01:14.950 00:01:14.960 millimetres from the ground here we can
00:01:17.680 00:01:17.690 see the wiring for the boiler under
00:01:19.480 00:01:19.490 circulating pump coming out from the
00:01:21.249 00:01:21.259 house this is not to the standard of the
00:01:23.350 00:01:23.360 home energy saving scheme this should be
00:01:25.270 00:01:25.280 in conduit and protected from the
00:01:26.680 00:01:26.690 elements and possible damage the pipe
00:01:29.109 00:01:29.119 work here is badly insulated the joints
00:01:31.240 00:01:31.250 are poor and the pipe work is at severe
00:01:32.859 00:01:32.869 risk of freezing this should ideally be
00:01:35.200 00:01:35.210 insulated with particular attention paid
00:01:37.120 00:01:37.130 around joints you will notice that the
00:01:39.910 00:01:39.920 oil line coming into the boiler casing
00:01:41.680 00:01:41.690 is not supported this is a possible risk
00:01:44.350 00:01:44.360 of damage and a possible leak it should
00:01:46.480 00:01:46.490 be cased and protected from potential
00:01:48.370 00:01:48.380 damage here we can see the wrong type of
00:01:52.210 00:01:52.220 fire valve is being used it should be
00:01:54.580 00:01:54.590 the remote type terminating at least one
00:01:56.770 00:01:56.780 meter away from the boiler with the
00:01:58.449 00:01:58.459 sensor located over the burner
00:02:01.649 00:02:01.659 in this shot we can see a circulating
00:02:04.260 00:02:04.270 pump and some pipe work both sides of
00:02:06.600 00:02:06.610 the circulating pump shall be crossed
00:02:08.219 00:02:08.229 bounded with a 10 square earth wire all
00:02:10.979 00:02:10.989 pipe work in the boiler casing should
00:02:12.660 00:02:12.670 also be carefully insulated with all
00:02:14.460 00:02:14.470 joints taped or glued looking at the
00:02:18.570 00:02:18.580 boiler logbook we can see that has not
00:02:20.550 00:02:20.560 been filled in the commissioning
00:02:22.500 00:02:22.510 certificate shall be filled in giving
00:02:24.390 00:02:24.400 all the contractor and boiler setup
00:02:26.160 00:02:26.170 details by filling in the boiler logbook
00:02:28.979 00:02:28.989 properly it helps to diagnose future
00:02:31.140 00:02:31.150 problems and operational and maintenance
00:02:32.850 00:02:32.860 errors now it is time to go around all
00:02:36.150 00:02:36.160 the radiators in the house making sure
00:02:38.460 00:02:38.470 that none of them are heating up on the
00:02:39.809 00:02:39.819 hot water circuit why it's doing this we
00:02:42.570 00:02:42.580 can check to see to their term estatic
00:02:44.370 00:02:44.380 radiator valves fitted when checking
00:02:47.220 00:02:47.230 these radiators it is important to keep
00:02:49.050 00:02:49.060 a lookout for leaks or possible damage
00:02:51.300 00:02:51.310 to might have occurred during the course
00:02:52.740 00:02:52.750 of the installation upon confirming do
00:02:55.110 00:02:55.120 none of the radiators are heating up on
00:02:56.970 00:02:56.980 the hot water circuit it is now time to
00:02:58.949 00:02:58.959 go to the hot press there are a number
00:03:02.100 00:03:02.110 of items to check at the hot press here
00:03:04.830 00:03:04.840 we can see a number of points that
00:03:07.050 00:03:07.060 aren't up to the standard here we can
00:03:09.509 00:03:09.519 see that there is no pipe insulation
00:03:11.160 00:03:11.170 within 1 meter of the cylinder all pipe
00:03:14.069 00:03:14.079 work within 1 meter of the cylinder must
00:03:16.229 00:03:16.239 be insulated
00:03:20.610 00:03:20.620 in this shot you noticed wiring is
00:03:23.220 00:03:23.230 untidy and at risk of getting damaged or
00:03:25.320 00:03:25.330 pulled out of connections by the
00:03:26.699 00:03:26.709 homeowner using their hot press here we
00:03:30.420 00:03:30.430 can see a junction box immersion switch
00:03:33.030 00:03:33.040 and a wiring center in this installation
00:03:35.970 00:03:35.980 the wiring is not up to standard as can
00:03:38.850 00:03:38.860 be seen from the clips here we can see a
00:03:41.430 00:03:41.440 junction box which strip connector is
00:03:43.170 00:03:43.180 used this is not the standard note the
00:03:45.539 00:03:45.549 damaged blue wire the emergence which
00:03:49.380 00:03:49.390 should have an immersion timer this is
00:03:52.140 00:03:52.150 not the case here this wiring Center
00:03:55.050 00:03:55.060 should have all wires clipped neatly
00:03:56.690 00:03:56.700 this earth wire is not to the standard
00:03:59.160 00:03:59.170 of the scheme as it is not ten square or
00:04:02.130 00:04:02.140 coming from the board or from an earth
00:04:03.809 00:04:03.819 rod in all circumstances where this has
00:04:06.720 00:04:06.730 come across it will have to be brought
00:04:08.280 00:04:08.290 up to the current standard it is now
00:04:11.309 00:04:11.319 time to see that the boiler interlock is
00:04:13.410 00:04:13.420 working correctly we do this by turning
00:04:15.960 00:04:15.970 the cylinder thermostat down to zero
00:04:19.099 00:04:19.109 when we turn this thermostat down to
00:04:21.750 00:04:21.760 zero we shall be able to hear or see the
00:04:24.180 00:04:24.190 motorized valve closing it is now time
00:04:31.260 00:04:31.270 to go and check that the boiler has
00:04:33.330 00:04:33.340 turned off this will indicate that the
00:04:36.089 00:04:36.099 hot water part of the boiler interlock
00:04:38.159 00:04:38.169 is installed correctly now we're back at
00:04:41.190 00:04:41.200 the boiler we can clearly see that the
00:04:43.350 00:04:43.360 boiler has not turned off this indicates
00:04:45.690 00:04:45.700 that the boiler interlock has not been
00:04:47.700 00:04:47.710 installed correctly this is an
00:04:49.500 00:04:49.510 electrical fault here we can see a 5 amp
00:04:53.520 00:04:53.530 fuse was in the spur this should be
00:04:56.100 00:04:56.110 removed and replaced with a 3 amp fuse
00:04:58.710 00:04:58.720 to comply with the current et Cie
00:05:00.990 00:05:01.000 regulations
00:05:03.420 00:05:03.430 we continue with the last part of our
00:05:05.700 00:05:05.710 inspection the next step is to test the
00:05:08.430 00:05:08.440 space heating circuit to see that it is
00:05:10.740 00:05:10.750 installed correctly we turn on the space
00:05:13.110 00:05:13.120 heating circuit now and give it a few
00:05:15.210 00:05:15.220 minutes to heat up when enough time has
00:05:17.999 00:05:18.009 elapsed for the radiators to heat up we
00:05:20.909 00:05:20.919 take a look around to make sure that
00:05:22.830 00:05:22.840 they are all heating and that none of
00:05:24.420 00:05:24.430 them are air locked are not working
00:05:25.860 00:05:25.870 properly this will often give an
00:05:28.499 00:05:28.509 indication if the system has been
00:05:30.330 00:05:30.340 balanced correctly this system has not
00:05:32.999 00:05:33.009 been balanced correctly this will lead
00:05:35.610 00:05:35.620 to inefficiencies
00:05:36.810 00:05:36.820 for example the boiler won't be in
00:05:39.060 00:05:39.070 condensing mode the last step of the
00:05:41.460 00:05:41.470 inspection is to go to the room
00:05:42.960 00:05:42.970 thermostat and turn it to zero while
00:05:46.110 00:05:46.120 snoring that this term estat is not in a
00:05:48.330 00:05:48.340 good location it is located in a room
00:05:51.360 00:05:51.370 with another source of heat an open fire
00:05:53.969 00:05:53.979 if lit this fire could lead to
00:05:56.100 00:05:56.110 determines that getting an inaccurate
00:05:58.080 00:05:58.090 reading and shorting down the system via
00:06:00.659 00:06:00.669 the boiler interlock when it should
00:06:02.580 00:06:02.590 still be turned on when the room
00:06:05.400 00:06:05.410 thermostat is set to zero we check to
00:06:07.860 00:06:07.870 see that the boiler has switched off
00:06:09.330 00:06:09.340 this indicates that the boiler interlock
00:06:12.150 00:06:12.160 is working on the space heating circuit
00:06:14.250 00:06:14.260 also the space heating side of the
00:06:16.980 00:06:16.990 boiler interlock has been installed
00:06:18.689 00:06:18.699 correctly as it turns off the boiler and
00:06:21.029 00:06:21.039 closes motorized valve we then reset the
00:06:25.230 00:06:25.240 room term stat and cylinder thermostat
00:06:27.360 00:06:27.370 to their original settings