How to replace heating and cooling indoor coils

WEBVTT
Kind: captions
Language: en

00:00:01.310
okay folks what I'm going to talk about
00:00:03.740 00:00:03.750 today is what it takes to replace an
00:00:06.380 00:00:06.390 indoor coil and why we have to replace
00:00:08.360 00:00:08.370 it after sometimes four or five years
00:00:10.879 00:00:10.889 six years we replace them all the time
00:00:13.669 00:00:13.679 and the reason for that I want you to
00:00:15.829 00:00:15.839 look at this particular coil here you've
00:00:17.750 00:00:17.760 got three dissimilar metals to start
00:00:20.120 00:00:20.130 with you've got copper you've got
00:00:22.550 00:00:22.560 aluminum you've got ten the same thing
00:00:26.210 00:00:26.220 here in this particular case you've got
00:00:27.710 00:00:27.720 the same copper ten in metal this one
00:00:30.050 00:00:30.060 even set in the waters here it's
00:00:31.429 00:00:31.439 actually just saying the water in itself
00:00:32.840 00:00:32.850 and it's called excess corrosion what
00:00:35.810 00:00:35.820 causes this is what we call forming
00:00:38.330 00:00:38.340 carry acid acid that takes a chemical
00:00:42.470 00:00:42.480 reaction of oxygen and water and these
00:00:46.130 00:00:46.140 dissimilar males it just corrodes and
00:00:48.080 00:00:48.090 breaks things down so the guy says well
00:00:51.229 00:00:51.239 what does it take to replace it I said
00:00:52.970 00:00:52.980 it's about three to four hours labor
00:00:54.650 00:00:54.660 okay
00:00:55.490 00:00:55.500 he says why I said well first of all
00:00:58.670 00:00:58.680 here's the reason here's your typical
00:01:00.380 00:01:00.390 air handler I've got a halfway full that
00:01:02.420 00:01:02.430 start we got to disconnect what we call
00:01:05.270 00:01:05.280 the SS two switches here okay we've got
00:01:08.750 00:01:08.760 to either pump the unit down or we have
00:01:12.050 00:01:12.060 to recover the refrigerant that's very
00:01:13.760 00:01:13.770 important okay then you got to come in
00:01:16.340 00:01:16.350 here you got to physically pull the coil
00:01:17.870 00:01:17.880 out take it out you're gonna get your
00:01:23.090 00:01:23.100 new coil say this is a new coil this is
00:01:25.789 00:01:25.799 demonstration take this new coil slide
00:01:27.950 00:01:27.960 it back in you've got a soldered all in
00:01:30.410 00:01:30.420 these copper fittings they all have to
00:01:32.450 00:01:32.460 be sorted with the torch torch okay once
00:01:35.840 00:01:35.850 you get all this complaint is DeeDee
00:01:37.310 00:01:37.320 gonna add a filter drier outside anytime
00:01:40.130 00:01:40.140 you open up your system you expose it to
00:01:42.410 00:01:42.420 contaminants you have to always put a
00:01:44.450 00:01:44.460 new filter drawer in if your technician
00:01:47.060 00:01:47.070 or your AC contract does not put this
00:01:49.249 00:01:49.259 device in he's taking short coding so
00:01:51.980 00:01:51.990 please don't allow that
00:01:53.139 00:01:53.149 then you go to do a nitrogen test you
00:01:55.460 00:01:55.470 want to put the nitric test up to work
00:01:57.020 00:01:57.030 and pressure the system okay which is I
00:01:59.990 00:02:00.000 tell my guys around 400 psi leave it on
00:02:02.959 00:02:02.969 for 15-20 minutes all right no leaks
00:02:05.959 00:02:05.969 then you want to pull it back and you
00:02:07.639 00:02:07.649 don't pull the back you down
00:02:08.919 00:02:08.929 about 4 or 500 microns okay that may
00:02:12.130 00:02:12.140 take 20 minutes 30 minutes an hour it
00:02:14.800 00:02:14.810 just depends on the lintel I set all
00:02:17.319 00:02:17.329 right now once you do all that you have
00:02:20.140 00:02:20.150 to go out there you have to fill it back
00:02:22.809 00:02:22.819 up with freon the 14 8 is what it
00:02:25.000 00:02:25.010 usually is most times these days and it
00:02:27.009 00:02:27.019 has to be sub cold correctly and this
00:02:29.140 00:02:29.150 thing has to run really because the 14 8
00:02:31.860 00:02:31.870 it has the molecules they just expand so
00:02:34.809 00:02:34.819 quickly so you can't just quickly charge
00:02:36.759 00:02:36.769 that like sometimes we did in the old
00:02:38.199 00:02:38.209 days with 22 ok so that's why it takes
00:02:42.009 00:02:42.019 long it takes pumping the unit down
00:02:44.860 00:02:44.870 pulling out the coil putting in the
00:02:48.339 00:02:48.349 filter dryer disconnecting all the SS 2
00:02:51.610 00:02:51.620 switches reconnecting all the SS 2
00:02:53.559 00:02:53.569 twisted putting in a nitrogen test doing
00:02:56.649 00:02:56.659 it vacuum so cool that's what it takes
00:02:59.679 00:02:59.689 homeowners it is a lot of work it's like
00:03:02.440 00:03:02.450 having a major component replace to your
00:03:04.360 00:03:04.370 car more like a head gasket or all that
00:03:07.659 00:03:07.669 stuff would have to pull all the valve
00:03:08.800 00:03:08.810 covers off it's a full day's job
00:03:10.420 00:03:10.430 sometimes depending on where the
00:03:11.619 00:03:11.629 location is if you have any questions
00:03:13.599 00:03:13.609 just go to Joan's air-conditioned comm
00:03:15.610 00:03:15.620 if you liked this video please share
00:03:17.129 00:03:17.139 please subscribe and please comment
00:03:19.210 00:03:19.220 thank you