HVAC - Cooling coil + Calculations ❄️❄️❄️

WEBVTT
Kind: captions
Language: en

00:00:02.000
[Applause]
00:00:04.300 00:00:04.310 hey there guys pulled here from the
00:00:06.499 00:00:06.509 engineering mindset calm in this video
00:00:09.020 00:00:09.030 we're going to be looking at the cooling
00:00:10.820 00:00:10.830 coils in an HVAC system to see what they
00:00:14.180 00:00:14.190 do how they work and how to ensure they
00:00:17.120 00:00:17.130 are operating efficiently and towards
00:00:19.490 00:00:19.500 the end of the video we're going to look
00:00:20.570 00:00:20.580 at some calculations for these also so
00:00:23.689 00:00:23.699 cooling coils are really common
00:00:25.660 00:00:25.670 component in HVAC systems and they
00:00:28.970 00:00:28.980 usually come in two forms the first one
00:00:31.339 00:00:31.349 being they are refrigerant they are fed
00:00:33.260 00:00:33.270 refrigerant directly from an AC unit as
00:00:36.819 00:00:36.829 you can see here so we've got the AC
00:00:40.040 00:00:40.050 unit outside and this is just piped
00:00:41.750 00:00:41.760 straight to the DX unit within the ahu
00:00:46.310 00:00:46.320 or the fan coil unit now you can always
00:00:50.450 00:00:50.460 tell if the cooling coil is a
00:00:52.459 00:00:52.469 refrigerant based and that's because
00:00:54.020 00:00:54.030 obviously it's got the expansion valves
00:00:56.389 00:00:56.399 here and they're usually directly
00:00:58.130 00:00:58.140 outside the coil and then you've also
00:01:01.849 00:01:01.859 got the this is this photo here is from
00:01:05.719 00:01:05.729 the inside of this coil and you can see
00:01:07.969 00:01:07.979 that splitting away there and feeding
00:01:10.160 00:01:10.170 off into multiple smaller tubes and off
00:01:13.340 00:01:13.350 into the cooling coil now this type of
00:01:16.789 00:01:16.799 cooling coil is controlled by there's a
00:01:19.789 00:01:19.799 capillary tube just inside underneath
00:01:22.190 00:01:22.200 this legging here and the tube rides up
00:01:24.649 00:01:24.659 and then comes through this through this
00:01:27.289 00:01:27.299 tube here and down low to the diaphragm
00:01:29.450 00:01:29.460 of the expansion valve so that controls
00:01:32.929 00:01:32.939 the refrigerant through them the meter
00:01:35.090 00:01:35.100 device there if you haven't already done
00:01:37.819 00:01:37.829 so I'd highly recommend you check out
00:01:39.830 00:01:39.840 our children video where we cover this
00:01:43.580 00:01:43.590 exact type of expansion valve and you
00:01:46.310 00:01:46.320 should see your link just above you now
00:01:48.190 00:01:48.200 now the other form of cooling coil
00:01:50.480 00:01:50.490 you're going to get is the chilled water
00:01:51.830 00:01:51.840 cooling coil and this is usually for an
00:01:54.530 00:01:54.540 equal economical point of view whereas
00:01:57.649 00:01:57.659 if you've got multiple 8h use or fan
00:02:00.139 00:02:00.149 coil units or you
00:02:02.210 00:02:02.220 a lot of cooling demand on the building
00:02:04.690 00:02:04.700 then it's probably going to be more
00:02:06.920 00:02:06.930 economical to have it from a centralized
00:02:09.170 00:02:09.180 system rather than a localized direct
00:02:12.380 00:02:12.390 expansion unit so this setup is more
00:02:15.590 00:02:15.600 common in very large buildings
00:02:17.920 00:02:17.930 whereas this setup it's much more common
00:02:20.990 00:02:21.000 in places like shops or small sites and
00:02:25.190 00:02:25.200 buildings so if the cooling coil is fed
00:02:27.800 00:02:27.810 by chilled water then it's going to look
00:02:29.540 00:02:29.550 to link a bit like this so the chilled
00:02:32.000 00:02:32.010 water flows in through the bottom and
00:02:33.760 00:02:33.770 flows through these passages here until
00:02:38.030 00:02:38.040 it makes its way to the top and then
00:02:39.800 00:02:39.810 exits back to the chiller and according
00:02:42.710 00:02:42.720 capacity for these types of cooling coil
00:02:45.350 00:02:45.360 they're just controlled by usually a
00:02:48.080 00:02:48.090 motorized valve or it could be manual
00:02:49.880 00:02:49.890 but certainly if you've got a BMS then
00:02:52.130 00:02:52.140 it will be from a motorized valve and
00:02:54.470 00:02:54.480 that just restricts some of the flow
00:02:56.720 00:02:56.730 going into it to meet the set point
00:02:58.730 00:02:58.740 whichever you've got for your low
00:03:00.920 00:03:00.930 temperature or off coil temperature now
00:03:04.490 00:03:04.500 there's some steps you can take to make
00:03:05.810 00:03:05.820 sure that your cooling core is operating
00:03:09.080 00:03:09.090 as efficiently as possible
00:03:10.910 00:03:10.920 and the first step is to ensure that the
00:03:14.290 00:03:14.300 the fins are cleaned regularly - all
00:03:19.550 00:03:19.560 these little sheets of metal that run in
00:03:22.160 00:03:22.170 between all the tubes they're known as
00:03:24.320 00:03:24.330 the fins and because the warm air that
00:03:27.290 00:03:27.300 comes in from the outside
00:03:29.420 00:03:29.430 usually condenses on the cooling coils
00:03:31.990 00:03:32.000 the surface of these can often be very
00:03:34.940 00:03:34.950 moist and any dirt or dust that has not
00:03:39.289 00:03:39.299 been captured by the filters will
00:03:41.720 00:03:41.730 usually end up sticking to this and all
00:03:44.210 00:03:44.220 that dirt it really just adds a layer of
00:03:46.400 00:03:46.410 insulation and stops the heat transfer
00:03:49.070 00:03:49.080 or the thermal energy transfer out of
00:03:52.310 00:03:52.320 these these tubes and into the fins so
00:03:55.910 00:03:55.920 the fins are there so that the chilled
00:03:58.610 00:03:58.620 water is passing through these tubes and
00:04:00.320 00:04:00.330 the fins just extract some of that cold
00:04:03.259 00:04:03.269 thermal energy out of there pulling out
00:04:06.979 00:04:06.989 into the air flow so the air passes
00:04:09.530 00:04:09.540 through the gaps in between and the fins
00:04:13.610 00:04:13.620 just extract some of that firmly
00:04:15.600 00:04:15.610 gee out and spread it across giving it
00:04:17.610 00:04:17.620 more chance for the air to take it away
00:04:19.789 00:04:19.799 so the more dust that covers these fins
00:04:22.790 00:04:22.800 the less chance the air has got to
00:04:25.860 00:04:25.870 actually come in contact with the cold
00:04:27.480 00:04:27.490 surface of the thin and take some of
00:04:30.600 00:04:30.610 that thermal energy away or transfer its
00:04:33.990 00:04:34.000 thermal energy back into the chilled
00:04:36.450 00:04:36.460 water another very common issue with
00:04:39.780 00:04:39.790 cooling coils is that the thins are very
00:04:42.630 00:04:42.640 delicate so any knock you know if you're
00:04:45.480 00:04:45.490 in there doing maintenance or anything
00:04:46.940 00:04:46.950 there's a high chance you're going to
00:04:48.780 00:04:48.790 knock these and that is going to damage
00:04:50.580 00:04:50.590 the fins like you can see in the photo
00:04:52.860 00:04:52.870 just here so what's happened here is
00:04:55.110 00:04:55.120 someone's obviously knocked into this
00:04:57.420 00:04:57.430 cooling coil and that's actually closed
00:04:59.820 00:04:59.830 the fin so it's pushed and shut so no
00:05:02.400 00:05:02.410 air can actually pass through there and
00:05:04.080 00:05:04.090 that means that no heat transfer will
00:05:06.390 00:05:06.400 occur
00:05:06.980 00:05:06.990 Frias obviously the the air would
00:05:09.600 00:05:09.610 normally pass through these gaps in
00:05:11.190 00:05:11.200 between the fins but here it's been
00:05:13.380 00:05:13.390 sealed seen it's been very careful when
00:05:16.350 00:05:16.360 working around these if you have got
00:05:19.020 00:05:19.030 some damaged fins and it's very easy to
00:05:21.180 00:05:21.190 repair you can actually buy one of these
00:05:23.510 00:05:23.520 condenser fin combs and they look a bit
00:05:25.980 00:05:25.990 like this and they're very cheap they're
00:05:27.960 00:05:27.970 around ten pounds ten dollars to buy and
00:05:30.960 00:05:30.970 you just you find the right size fin
00:05:34.290 00:05:34.300 fittings that you've got and then you
00:05:36.360 00:05:36.370 just put it in like a comb and you push
00:05:38.940 00:05:38.950 against that up and down a few times and
00:05:42.810 00:05:42.820 that will actually straighten out all
00:05:44.520 00:05:44.530 the fins back to new now I've left some
00:05:48.390 00:05:48.400 links in the description just for where
00:05:50.850 00:05:50.860 you can buy these from they're a very
00:05:53.670 00:05:53.680 useful tool I really recommend any HVAC
00:05:57.330 00:05:57.340 engineer that have one of these so if
00:06:00.060 00:06:00.070 you just scroll down and hit the show
00:06:01.890 00:06:01.900 more button and you can find those
00:06:03.600 00:06:03.610 things below another important step for
00:06:06.030 00:06:06.040 your cooling coils if they are chilled
00:06:08.640 00:06:08.650 water fed then you should check that the
00:06:13.070 00:06:13.080 cooling coils in your building are being
00:06:16.590 00:06:16.600 fed chilled water and the water should
00:06:18.000 00:06:18.010 be entering through the bottom and then
00:06:21.030 00:06:21.040 rising up through that going against
00:06:23.250 00:06:23.260 gravity which gives it more chance
00:06:25.200 00:06:25.210 through turbulator become turbulent in
00:06:27.570 00:06:27.580 there and give up
00:06:28.770 00:06:28.780 with that thermal energy and then make
00:06:31.080 00:06:31.090 its way out at the top if it's been
00:06:33.330 00:06:33.340 piped incorrectly so the chilled water
00:06:34.980 00:06:34.990 is entering through the top and leaving
00:06:37.440 00:06:37.450 through the bottom if you were supply /
00:06:39.570 00:06:39.580 and the other way the correct way then
00:06:41.700 00:06:41.710 you're probably going to see about five
00:06:43.409 00:06:43.419 anywhere between five and fifteen
00:06:45.120 00:06:45.130 percent increase in effectiveness from
00:06:47.370 00:06:47.380 that but if you do find one on your site
00:06:49.470 00:06:49.480 please first check with your
00:06:50.700 00:06:50.710 manufacturer to make sure that it has
00:06:52.710 00:06:52.720 been fully designed for that operation
00:06:55.129 00:06:55.139 another check you should have a look at
00:06:57.600 00:06:57.610 on your site is if the the inlet for the
00:07:00.780 00:07:00.790 chilled water should always be on the
00:07:02.520 00:07:02.530 right hand side the furthest part away
00:07:04.800 00:07:04.810 from the direction of flow so if your
00:07:08.010 00:07:08.020 cooling coil is the other way around
00:07:09.530 00:07:09.540 then it's actually back to front so if
00:07:11.760 00:07:11.770 the if the inlet is on the face closest
00:07:14.940 00:07:14.950 to the direction of airflow then this
00:07:17.250 00:07:17.260 has been installed incorrectly also
00:07:19.219 00:07:19.229 unless again the manufacturer has
00:07:21.360 00:07:21.370 specifically designed it for that
00:07:23.100 00:07:23.110 purpose so please check with them okay
00:07:25.890 00:07:25.900 so let's have a look at some some basic
00:07:27.990 00:07:28.000 cooling coil calculations so here we've
00:07:30.780 00:07:30.790 got some sort of cooling device being
00:07:32.370 00:07:32.380 either a fan coil unit or an a hate you
00:07:35.300 00:07:35.310 essentially performing the same task but
00:07:37.770 00:07:37.780 on a larger scale for an ahu and we know
00:07:41.070 00:07:41.080 that this fan here is pulling in air at
00:07:44.219 00:07:44.229 a volume flow rate of two meters cube
00:07:47.909 00:07:47.919 per second we're going to temperature
00:07:50.010 00:07:50.020 probe here and we can measure that that
00:07:52.409 00:07:52.419 air coming in is coming in at a
00:07:54.360 00:07:54.370 temperature of 30 degrees Celsius and
00:07:56.460 00:07:56.470 from the BMS or maybe a humidity sensor
00:07:59.909 00:07:59.919 we can tell that the air coming in has a
00:08:02.940 00:08:02.950 relative humidity of 70 percent and with
00:08:06.240 00:08:06.250 these two values here that means we can
00:08:08.100 00:08:08.110 look up all the these other values here
00:08:11.130 00:08:11.140 such as the specific volume the enthalpy
00:08:13.620 00:08:13.630 and also the specific humidity and
00:08:16.770 00:08:16.780 you'll have to look these up in the air
00:08:17.940 00:08:17.950 property tables you can just google
00:08:20.190 00:08:20.200 these it's very quick and easy to do or
00:08:22.740 00:08:22.750 just find an online air properties
00:08:24.810 00:08:24.820 calculator now the supply air that's
00:08:27.930 00:08:27.940 coming out of the fan coil unit or the
00:08:29.610 00:08:29.620 air here tube we're measuring it here
00:08:31.830 00:08:31.840 and we know that that air is coming out
00:08:33.750 00:08:33.760 of 15 degrees Celsius with a relative
00:08:36.570 00:08:36.580 humidity of 100% and from those two
00:08:40.079 00:08:40.089 values we can then
00:08:41.550 00:08:41.560 cup the enthalpy and also the specific
00:08:43.890 00:08:43.900 humidity for this airflow also so
00:08:47.640 00:08:47.650 obviously that air has cooled down from
00:08:49.740 00:08:49.750 30 degrees Celsius down to 15 degrees
00:08:52.470 00:08:52.480 Celsius and that's because the cooling
00:08:54.600 00:08:54.610 coil here is an operation so flowing
00:08:59.730 00:08:59.740 through this cooling coil is the chilled
00:09:02.280 00:09:02.290 water and that is flowing at a rate of
00:09:04.650 00:09:04.660 four point six seven kilograms per
00:09:06.840 00:09:06.850 second the water coming in is at six
00:09:10.079 00:09:10.089 degrees Celsius and from that we can
00:09:13.710 00:09:13.720 look up and tell that the specific heat
00:09:16.140 00:09:16.150 capacity is at four point two kilojoules
00:09:18.990 00:09:19.000 per kilogram per Kelvin but we don't
00:09:22.680 00:09:22.690 know yet what the temperature out is
00:09:25.860 00:09:25.870 going to be on that core but we can
00:09:27.390 00:09:27.400 calculate that also now this air is also
00:09:32.250 00:09:32.260 condensing because it's coming in very
00:09:34.170 00:09:34.180 warm and leaving very cool at a hundred
00:09:36.930 00:09:36.940 percent relative humidity so that the
00:09:40.110 00:09:40.120 moisture in that air is condensing on
00:09:42.210 00:09:42.220 this cooling coil and that is then
00:09:44.340 00:09:44.350 flowing a way out to drain and we know
00:09:48.030 00:09:48.040 that that water is going to be at a
00:09:50.400 00:09:50.410 temperature of this out here so that's
00:09:52.800 00:09:52.810 going to be at fifteen degrees Celsius
00:09:54.420 00:09:54.430 and and we can look that up the enthalpy
00:09:57.450 00:09:57.460 for that which will be you'll have the
00:09:59.820 00:09:59.830 fine ease in the saturated steam tables
00:10:01.950 00:10:01.960 and that you'll see that there is going
00:10:04.860 00:10:04.870 to be at 63 kilojoules per kilogram and
00:10:07.980 00:10:07.990 we can also calculate how much water is
00:10:11.100 00:10:11.110 actually flowing out of there from this
00:10:12.540 00:10:12.550 air that's coming in so of this air
00:10:15.120 00:10:15.130 that's coming in there's obviously two
00:10:16.140 00:10:16.150 parts to that there is air that's coming
00:10:19.020 00:10:19.030 in and then there's also moisture which
00:10:20.820 00:10:20.830 is in the end so we can calculate how
00:10:23.190 00:10:23.200 much just pure air is in there so that
00:10:25.560 00:10:25.570 it's called the dry dry air and the the
00:10:28.770 00:10:28.780 mass flow rate of that coming in the
00:10:30.510 00:10:30.520 amount of flow rate of air coming in
00:10:34.070 00:10:34.080 without any moisture that is the m dot
00:10:37.710 00:10:37.720 the dot just represents a rate of flow a
00:10:41.030 00:10:41.040 represents the the air
00:10:43.150 00:10:43.160 so it's the volume flow rate you can see
00:10:46.480 00:10:46.490 up here divided by the specific volume
00:10:49.300 00:10:49.310 also of that air coming in and obviously
00:10:52.330 00:10:52.340 that is a number there is specific to
00:10:55.480 00:10:55.490 the air at these conditions so when we
00:11:00.070 00:11:00.080 drop these numbers in which are just
00:11:01.450 00:11:01.460 coming from up here this comes out at
00:11:04.270 00:11:04.280 two point two two kilograms per second
00:11:06.790 00:11:06.800 of air dry air coming into this cooling
00:11:09.940 00:11:09.950 unit I also mentioned that there is
00:11:12.460 00:11:12.470 condensate water that's water that's
00:11:14.530 00:11:14.540 being extracted from this warm air and
00:11:17.380 00:11:17.390 it's being discharged down to drain so
00:11:19.930 00:11:19.940 we can calculate the flow rate of that
00:11:21.700 00:11:21.710 as well so so the condensate mass flow
00:11:27.100 00:11:27.110 rate that's the water so it's MDOT and
00:11:29.680 00:11:29.690 the W represents just water and we can
00:11:34.210 00:11:34.220 use this formula here which is the mass
00:11:36.610 00:11:36.620 flow at the flow rate of the air which
00:11:38.650 00:11:38.660 we just calculated multiplied by the
00:11:42.700 00:11:42.710 difference in the specific humidity and
00:11:46.450 00:11:46.460 that gives us naught point naught to two
00:11:48.460 00:11:48.470 kilograms per second and that's of water
00:11:50.940 00:11:50.950 flowing out of this so from all this we
00:11:54.850 00:11:54.860 can then calculate the cooling load and
00:11:57.310 00:11:57.320 that's represented by the Q that formula
00:12:01.570 00:12:01.580 is just the summary of the mass flow
00:12:05.260 00:12:05.270 rate of the air multiplied by the
00:12:07.770 00:12:07.780 difference in enthalpy across these two
00:12:11.020 00:12:11.030 air streams in addition to
00:12:13.890 00:12:13.900 multiplication of the mass flow rate of
00:12:16.510 00:12:16.520 the water multiplied by the enthalpy of
00:12:19.540 00:12:19.550 the condensate water also and you can
00:12:22.690 00:12:22.700 see I've color-coded these numbers as
00:12:24.340 00:12:24.350 well so you should be able to just trace
00:12:26.320 00:12:26.330 these out if you was to get stuck trying
00:12:27.880 00:12:27.890 to work this out yourself so when we
00:12:30.520 00:12:30.530 drop these numbers in you should see
00:12:32.350 00:12:32.360 that this comes out at seventy eight
00:12:34.390 00:12:34.400 point five kilojoules per second which
00:12:36.700 00:12:36.710 is also obviously seventy eight point
00:12:39.280 00:12:39.290 five kilowatts so that means that this
00:12:42.220 00:12:42.230 cooling coil is extracting seventy eight
00:12:45.460 00:12:45.470 point five kilowatts or thermal energy
00:12:47.650 00:12:47.660 from this air stream and once we know
00:12:50.650 00:12:50.660 that we can then calculate what the
00:12:53.170 00:12:53.180 water off temperature is going to be so
00:12:55.840 00:12:55.850 vit
00:12:56.420 00:12:56.430 water the chilled water is leaving this
00:12:58.700 00:12:58.710 cooling coil what temperature that's
00:13:00.829 00:13:00.839 going to be at so the temperature out
00:13:03.860 00:13:03.870 the T out is equal to temperature in
00:13:07.730 00:13:07.740 plus the cooling load divided by the
00:13:11.000 00:13:11.010 mass flow rate of this water that's
00:13:13.550 00:13:13.560 passing through and that multiplied
00:13:16.490 00:13:16.500 against the specific heat capacity again
00:13:19.400 00:13:19.410 all these figures are color-coded so you
00:13:21.260 00:13:21.270 should be able to just find these and
00:13:23.420 00:13:23.430 plot them in if you've got an example
00:13:24.620 00:13:24.630 yourself to work out so when we drop
00:13:27.710 00:13:27.720 these figures in you should see that the
00:13:29.540 00:13:29.550 temperature of the T out is equal to ten
00:13:33.079 00:13:33.089 degrees Celsius
00:13:34.100 00:13:34.110 so that water is coming in at six
00:13:36.829 00:13:36.839 degrees Celsius and leaving at 10 degree
00:13:39.350 00:13:39.360 Celsius going back to the chiller okay
00:13:42.139 00:13:42.149 that is it for this video thank you very
00:13:43.760 00:13:43.770 much for watching if you've got any
00:13:45.590 00:13:45.600 questions please leave them in the
00:13:46.730 00:13:46.740 comment section below don't forget to
00:13:49.130 00:13:49.140 Like and subscribe to the channel and
00:13:50.750 00:13:50.760 feel free to share the video with anyone
00:13:53.690 00:13:53.700 you think it might help also once again
00:13:56.269 00:13:56.279 thanks for watching
Office location
Engineering company LOTUS®
Russia, Ekaterinburg, Lunacharskogo street, 240/12

Phone: +7 343 216 77 75

E-mail: info@lotus1.ru

Sales phone

Russia: +7 343 216 77 75

WhatsApp: +79122710308