Ravenheat boiler repair. This boiler has fault 28. Boiler not turning on.

WEBVTT
Kind: captions
Language: en

00:00:00.000
hey welcome to eating geeks in this
00:00:02.720 00:00:02.730 video here I'm gonna show you a Raven
00:00:04.640 00:00:04.650 heat boiler that all it needed was a
00:00:06.470 00:00:06.480 little bit more time spent on it by the
00:00:09.290 00:00:09.300 previous engineer if we had had um met
00:00:11.480 00:00:11.490 the boiler would have been fixed but you
00:00:13.669 00:00:13.679 didn't so that's where I come in
00:00:15.530 00:00:15.540 and I went there and got the boiler
00:00:17.120 00:00:17.130 fixed enjoy it
00:00:19.519 00:00:19.529 happy Father's Day to all the dads out
00:00:21.290 00:00:21.300 there I've got three boys here myself I
00:00:24.080 00:00:24.090 have plenty of plenty busy that's for
00:00:26.870 00:00:26.880 sure
00:00:27.230 00:00:27.240 anyway enjoy the video
00:00:31.220 00:00:31.230 [Music]
00:00:44.139 00:00:44.149 I hear y'all today this Ravens eat 28
00:00:54.939 00:00:54.949 flashing don't know what that means is
00:00:58.180 00:00:58.190 this one but this one has two reports on
00:01:01.840 00:01:01.850 it
00:01:02.610 00:01:02.620 no news you're not ready we can't be
00:01:07.120 00:01:07.130 it's not most call it things I say let's
00:01:11.350 00:01:11.360 have a look
00:01:11.980 00:01:11.990 get into and see more suave
00:01:19.050 00:01:19.060 so here we are covers off inside it so
00:01:22.600 00:01:22.610 do my usual thing of looking at
00:01:24.700 00:01:24.710 everything so we've got flu stat quite
00:01:27.429 00:01:27.439 electrodes this we spark
00:01:30.429 00:01:30.439 that'll be rectification we have an NTC
00:01:34.270 00:01:34.280 and overheat gas valve we have a firm
00:01:38.620 00:01:38.630 with two plugs on it so that's going to
00:01:40.330 00:01:40.340 be 240 and 24 volt
00:01:42.700 00:01:42.710 they'll be 24 volt they look control
00:01:44.830 00:01:44.840 stuff and that we 240 down there to make
00:01:46.840 00:01:46.850 it run spark generator there we have the
00:01:52.840 00:01:52.850 bits that probably run so let's open
00:01:58.199 00:01:58.209 this up so we can have a better look
00:02:00.639 00:02:00.649 inside there but as you can see this top
00:02:03.190 00:02:03.200 section nothing new in there also normal
00:02:06.550 00:02:06.560 bits and bobs you see in boilers where
00:02:09.850 00:02:09.860 there's this watermark on it but anyway
00:02:12.070 00:02:12.080 worry about that after assuming get the
00:02:14.589 00:02:14.599 thing to work actually right now I don't
00:02:16.839 00:02:16.849 even know what this fault code is so I'm
00:02:20.229 00:02:20.239 actually to look that up using the data
00:02:22.059 00:02:22.069 badge to find the manual so but Raven
00:02:26.949 00:02:26.959 eat technical are very good so Devon eat
00:02:29.920 00:02:29.930 all you McCall okay so I panels come off
00:02:34.210 00:02:34.220 nice and easy it's great access how this
00:02:41.430 00:02:41.440 comes out let's give us room to have a
00:02:44.620 00:02:44.630 look well let's look at the forecast
00:02:46.630 00:02:46.640 there is something by the way the reason
00:02:47.890 00:02:47.900 I'm going in here is someone's ordered
00:02:49.300 00:02:49.310 up a diaphragm a diaphragm or a micro
00:02:53.949 00:02:53.959 switch so somewhere in there it's a
00:02:55.180 00:02:55.190 pressure differential switch for the
00:02:56.830 00:02:56.840 pump I think pump or even switch so I'll
00:02:59.920 00:02:59.930 just find that somewhere in there but I
00:03:04.150 00:03:04.160 will let me look up this first one they
00:03:05.979 00:03:05.989 let me have cut this fault here go on
00:03:09.280 00:03:09.290 give it a click
00:03:10.569 00:03:10.579 it's not gonna hurt is it there's
00:03:13.539 00:03:13.549 default code okay so this does mean pump
00:03:18.759 00:03:18.769 proofing error so I'm gonna get this lot
00:03:21.879 00:03:21.889 out
00:03:24.640 00:03:24.650 and uh and see if there is a problem at
00:03:29.690 00:03:29.700 a pump but so far it was nothing too
00:03:33.830 00:03:33.840 stressful here and see how this PCB box
00:03:36.410 00:03:36.420 comes out okay so this doesn't actually
00:03:42.010 00:03:42.020 it was very much room here the thing
00:03:45.590 00:03:45.600 that we need seth has been ordered you
00:03:49.460 00:03:49.470 can't really see let me move the phone
00:03:50.990 00:03:51.000 I'm gonna flip you upside-down and it's
00:03:55.790 00:03:55.800 back there if you look that is the
00:03:59.300 00:03:59.310 microswitch there some crusher diff is
00:04:05.330 00:04:05.340 there coffee on the pump this look for
00:04:07.280 00:04:07.290 you again
00:04:07.610 00:04:07.620 I have enough on the line there's the
00:04:18.560 00:04:18.570 pressure diff little bit all got ice
00:04:23.330 00:04:23.340 there
00:04:24.130 00:04:24.140 yeah yeah I'm guess you pulled up on
00:04:28.130 00:04:28.140 power for that you got you've got be
00:04:30.590 00:04:30.600 taking that pump out to get to that it's
00:04:32.870 00:04:32.880 fresh in this situation there if they
00:04:35.240 00:04:35.250 have to so this let's test it to make
00:04:39.020 00:04:39.030 sure that is the fault though okay so
00:04:44.050 00:04:44.060 this is the pressure difficult there's
00:04:46.400 00:04:46.410 the water pressure switch there and
00:04:48.040 00:04:48.050 here's the mics which off the pressure
00:04:52.070 00:04:52.080 differential so this is this these two
00:05:00.050 00:05:00.060 are you know daisy chained together
00:05:02.030 00:05:02.040 so in theory if we were to test across
00:05:05.540 00:05:05.550 the this white connection here and the
00:05:09.620 00:05:09.630 blue connection back here we should have
00:05:12.980 00:05:12.990 continuity okay going through both of
00:05:16.730 00:05:16.740 these switches if we have that we won't
00:05:21.080 00:05:21.090 have it initially what I'll have to do
00:05:23.029 00:05:23.039 is go test on the pushed and my
00:05:24.650 00:05:24.660 extrusion here to click it and if we
00:05:26.870 00:05:26.880 then get continuity through all of that
00:05:28.820 00:05:28.830 together let's go right here if we then
00:05:32.839 00:05:32.849 got
00:05:35.120 00:05:35.130 if we then get continuity across all of
00:05:38.310 00:05:38.320 this lot we know the wall pressure
00:05:39.810 00:05:39.820 switch is good and this micro switch is
00:05:41.820 00:05:41.830 good okay so then what we will do is we
00:05:45.000 00:05:45.010 will get the pump to run and make sure
00:05:46.890 00:05:46.900 the pin comes out of the pressured if
00:05:49.500 00:05:49.510 switch at the back there if the ping
00:05:51.900 00:05:51.910 comes out great if it doesn't then its
00:05:54.450 00:05:54.460 pump out get the pressure dip and see
00:05:58.050 00:05:58.060 what's going on with it
00:05:59.070 00:05:59.080 so first we're going to do a self-test
00:06:00.840 00:06:00.850 for this the wall pressure switch and
00:06:02.790 00:06:02.800 the pressure differential switch so we
00:06:06.030 00:06:06.040 always set up on them right
00:06:09.380 00:06:09.390 so that is 41 that's what we want killer
00:06:14.400 00:06:14.410 ohms
00:06:14.940 00:06:14.950 now I'm gonna click the mic switch yeah
00:06:25.890 00:06:25.900 so that shows the the war pressure
00:06:28.740 00:06:28.750 switches doing what's meant to do and
00:06:31.560 00:06:31.570 then when this clicks this is doing what
00:06:34.440 00:06:34.450 it's meant to do this micro switch okay
00:06:36.120 00:06:36.130 I'll contain that of resistance cross
00:06:37.920 00:06:37.930 these leads on one more with mirrors
00:06:39.570 00:06:39.580 about one-and-a-half ohms so that point
00:06:42.090 00:06:42.100 has been that one point three ohms now
00:06:45.290 00:06:45.300 you can hear that click nicely so that's
00:06:47.670 00:06:47.680 what I'm doing okay
00:06:53.090 00:06:53.100 and so these these are these two
00:06:58.410 00:06:58.420 sentences being daisy chained here okay
00:07:01.290 00:07:01.300 it's just like other boilers like for
00:07:04.740 00:07:04.750 instance the Worcester green star the
00:07:08.490 00:07:08.500 Worcester green star jr. off the top of
00:07:11.370 00:07:11.380 my head that that is the flu sensor and
00:07:13.590 00:07:13.600 the green overheats down the heat
00:07:15.330 00:07:15.340 exchanger are daisy chained like this so
00:07:18.990 00:07:19.000 you test both in one go
00:07:21.170 00:07:21.180 I've a Worcester the old jr. that was
00:07:23.940 00:07:23.950 that junior RSF that's got the warp
00:07:27.360 00:07:27.370 pressure sensor and the overheats down
00:07:28.950 00:07:28.960 the top right that heat exchanger that
00:07:30.540 00:07:30.550 daisy chain just like this so basically
00:07:35.190 00:07:35.200 it's quite easy to to test them so it
00:07:38.790 00:07:38.800 smoke ways it's then linked stuff out to
00:07:41.010 00:07:41.020 make the boiler run sis or 240 volt
00:07:43.080 00:07:43.090 stuff you can just link it out and if
00:07:46.740 00:07:46.750 the boiler them runs and fires and runs
00:07:48.840 00:07:48.850 fine you know you've got a sensor issue
00:07:51.840 00:07:51.850 I wouldn't recommend you do it but it's
00:07:53.430 00:07:53.440 just something you can do I saying that
00:07:58.890 00:07:58.900 I might do that here just to get just to
00:08:00.780 00:08:00.790 prove that this isn't blocked and the
00:08:02.670 00:08:02.680 pump and all that's working currently or
00:08:04.470 00:08:04.480 may just do that and let's get it
00:08:06.570 00:08:06.580 running and have a look and see if you
00:08:09.180 00:08:09.190 can see the person if they're just
00:08:10.620 00:08:10.630 hiding see if that pin moves out that
00:08:13.740 00:08:13.750 pressure diff
00:08:22.980 00:08:22.990 I'm trolling me like that pinned down
00:08:29.170 00:08:29.180 nicely it's just 20 I again though oh
00:08:33.790 00:08:33.800 that's okay it says 28 because the I
00:08:36.579 00:08:36.589 have the thing not connected to this
00:08:40.829 00:08:40.839 let's try and focus on this a little
00:08:44.350 00:08:44.360 reset this boiler turn the power back on
00:08:54.870 00:08:54.880 that pin moved out that move back in
00:09:02.400 00:09:02.410 right that seems to work something for
00:09:05.079 00:09:05.089 me so we've got 28 again so let's put
00:09:07.930 00:09:07.940 the mic switch back on I'm running
00:09:29.600 00:09:29.610 or this early you know catch
00:09:34.840 00:09:34.850 you know talk to the customer I could
00:09:39.190 00:09:39.200 hear what going through all of this
00:09:40.540 00:09:40.550 nicely they obviously any air you can
00:09:44.320 00:09:44.330 hear air but any air will limit the
00:09:46.540 00:09:46.550 effectiveness of that diaphragm so what
00:09:51.610 00:09:51.620 was tower would happen if the external
00:09:54.880 00:09:54.890 controls stopped calling for heat so
00:09:57.450 00:09:57.460 then a widest is wide like this but
00:09:59.800 00:09:59.810 that's the external controls there so if
00:10:03.010 00:10:03.020 I turn this off by valve sure close
00:10:30.189 00:10:30.199 elves obviously opening or he clicks
00:10:32.809 00:10:32.819 when the step that pump kicked in
00:10:44.130 00:10:44.140 [Laughter]
00:10:47.470 00:10:47.480 and so let's try that again shall we
00:10:49.380 00:10:49.390 turn that off
00:10:53.130 00:10:53.140 00:10:54.410 00:10:54.420 right away it lost its demands
00:10:56.610 00:10:56.620 00:11:03.040 00:11:03.050 that light is a lawnmower
00:11:05.750 00:11:05.760 that is known or what mister this song
00:11:13.340 00:11:13.350 turn that back on love Harriet line
00:11:20.360 00:11:20.370 00:11:37.860 00:11:37.870 so the long tones are expired in there
00:11:40.900 00:11:40.910 anyway I've left this running for a
00:11:43.690 00:11:43.700 little long and you can see this issue
00:11:49.080 00:11:49.090 obviously I'm gonna drive in on the
00:11:51.190 00:11:51.200 vessel but what's funny is I've done a
00:11:53.980 00:11:53.990 bit of digging I found out a bit more
00:11:55.270 00:11:55.280 information okay so what happened here
00:11:57.580 00:11:57.590 was the boiler continually lost pressure
00:12:02.670 00:12:02.680 and every few days the customer had
00:12:04.810 00:12:04.820 stopped the pressure up and reset their
00:12:06.610 00:12:06.620 28th flashing here okay now that's
00:12:09.640 00:12:09.650 probably the cause of that and the
00:12:11.680 00:12:11.690 engineer knows why that's done that and
00:12:13.330 00:12:13.340 what's gonna happen and why there'll be
00:12:15.310 00:12:15.320 no war and it in a little bit so I'm
00:12:17.410 00:12:17.420 gonna fix that issue so what happened
00:12:22.090 00:12:22.100 was the engineer came and replaced this
00:12:24.510 00:12:24.520 okay because this had stopped working as
00:12:26.770 00:12:26.780 far as they are aware now what I think
00:12:28.780 00:12:28.790 happened is when he replaced this he
00:12:31.120 00:12:31.130 introduced a lot of air into the system
00:12:32.890 00:12:32.900 or into the boiler which is what we
00:12:35.380 00:12:35.390 could hear when it was first trying to
00:12:36.670 00:12:36.680 run and pressure differential switches
00:12:44.110 00:12:44.120 just not only takes pressure
00:12:46.610 00:12:46.620 differential switches but that one back
00:12:48.770 00:12:48.780 there don't like air any bit of air can
00:12:52.100 00:12:52.110 cause it lots of sense because the airs
00:12:54.290 00:12:54.300 are consults on it it absorbs the
00:12:57.050 00:12:57.060 pressure from the pump
00:12:58.490 00:12:58.500 so pressure differential switch won't
00:13:00.230 00:13:00.240 see it so anyway let me deal with this
00:13:04.030 00:13:04.040 this pressure issue this rising which
00:13:07.550 00:13:07.560 that's an engineer will notice quite a
00:13:08.900 00:13:08.910 basic thing so I want to get on with
00:13:12.680 00:13:12.690 that and then retest to boil up when
00:13:16.670 00:13:16.680 ugly field is born are after dealing
00:13:18.200 00:13:18.210 with that issue I'm going to vent the
00:13:19.670 00:13:19.680 pressure from the air out there time to
00:13:24.380 00:13:24.390 get over there so just for your
00:13:38.510 00:13:38.520 information boy that's got no drain off
00:13:40.900 00:13:40.910 it's got a
00:13:47.000 00:13:47.010 those help see that it's got a decent
00:13:50.930 00:13:50.940 POV with good access so I drank juice in
00:13:54.710 00:13:54.720 the POV which is just here and then I'll
00:13:58.400 00:13:58.410 whip the head off
00:13:59.590 00:13:59.600 cleaned it greased it put it back
00:14:01.460 00:14:01.470 together
00:14:01.950 00:14:01.960 00:14:15.540 00:14:15.550 lovely jubbly
00:14:24.340 00:14:24.350 we're you good I
00:14:28.329 00:14:28.339 go about it so
00:14:40.160 00:14:40.170 okay so as you see that the real simple
00:14:43.400 00:14:43.410 thing just a bit of air in the system if
00:14:45.290 00:14:45.300 there are engine is spent that a little
00:14:46.850 00:14:46.860 bit more time we've had it fixed so
00:14:49.700 00:14:49.710 remember guys you can sponsor me on
00:14:51.800 00:14:51.810 patron and I wanna Instagram Facebook
00:14:54.410 00:14:54.420 and he sports much appreciated all the
00:14:57.950 00:14:57.960 links are down below blah blah blah all
00:14:59.930 00:14:59.940 that nonsense thanks a lot