Temperature Interval Method for Heat Exchanger Networks

WEBVTT
Kind: captions
Language: en

00:00:02.500 --> 00:00:07.839
In this video we're going to focus on a specific
design approach for creating a heat exchanger
00:00:07.839 --> 00:00:12.940
network, and we're just going to work through
an example problem that's shown here, where
00:00:12.940 --> 00:00:18.020
we have four streams that are going through
a process, and they have certain inlet temperatures
00:00:18.020 --> 00:00:25.109
and outlet temperatures, and just to clarify
the inlet temperature of 30 degrees exits
00:00:25.109 --> 00:00:32.960
at an outlet temperature of 135, which means
that the inlet temperature of 180 exits at
00:00:32.960 --> 00:00:39.040
60, so looking at these temperatures you can
see that we have two hot streams and two cold
00:00:39.040 --> 00:00:40.040
streams.
00:00:40.040 --> 00:00:46.579
So I am going to go through an approach step-by-step
using a temperature interval method to figure
00:00:46.579 --> 00:00:51.830
out what our minimum energy requirements,
MER, are going to be in this process.
00:00:51.830 --> 00:00:57.450
So we're going to specifically focus on trying
to minimize the utility loads that come in
00:00:57.450 --> 00:01:02.109
from both the hot side and a cold side of
a process that we would need to off balance
00:01:02.109 --> 00:01:06.740
any energy that we would have to provide or
take away from these four streams.
00:01:06.740 --> 00:01:10.220
So the first step is to create a table for
our streams.
00:01:10.220 --> 00:01:17.950
So T(s) stands for our source temperature,
so that's really our inlet, and T(t) stands
00:01:17.950 --> 00:01:20.270
for our target temperature.
00:01:20.270 --> 00:01:27.200
C is our heat capacity flow rate, and that's
just something you've seen before as the flow
00:01:27.200 --> 00:01:33.710
rate times a specific heat, and you could
see that the units on this are an energy per
00:01:33.710 --> 00:01:39.030
temperature, so that accounts for our mass
flow rates for each stream.
00:01:39.030 --> 00:01:44.780
So I'll start filling in the temperatures
here, so we were given the heat capacity flow
00:01:44.780 --> 00:01:49.300
rate values in the problem statement, so that's
something I am going to write in here, and
00:01:49.300 --> 00:01:57.240
I have this assumption that these heat capacity
flow rates are going to stay constant as a
00:01:57.240 --> 00:02:05.130
function of temperature, or in other words
we would write that C is not a function of
00:02:05.130 --> 00:02:10.090
temperature, and you know that if we had a
phase change for any of these streams we would
00:02:10.090 --> 00:02:14.040
definitely have to account for the energy
associated with that, or a reaction that might
00:02:14.040 --> 00:02:19.480
be occurring, and for many species the heat
capacity won't be constant over a large range
00:02:19.480 --> 00:02:24.040
in temperatures, and that's something that
you may have to use in breaking up the streams
00:02:24.040 --> 00:02:25.880
into those specific intervals.
00:02:25.880 --> 00:02:33.489
So the first thing we could do is just calculate
a heat transfer for each of the streams where
00:02:33.489 --> 00:02:39.840
we know that the heat transfer rate is going
to be mC delta T, and we've already been given
00:02:39.840 --> 00:02:46.060
this mC as our heat capacity ratio, so it's
just a matter of multiplying the heat capacity
00:02:46.060 --> 00:02:50.629
flow rate by this temperature difference,
and I'll fill that in.
00:02:50.629 --> 00:02:57.930
So you could see that our cold load here on
the cold side adds up to 510, and our hot
00:02:57.930 --> 00:03:02.170
load adds up to 480.
00:03:02.170 --> 00:03:06.100
So we know in this case that our difference
between the two streams is 30 kW, and we'll
00:03:06.100 --> 00:03:10.040
have to determine later on how to account
for these 30 kW.
00:03:10.040 --> 00:03:13.900
Now just a note this is not the minimum energy
requirement that we're looking for, because
00:03:13.900 --> 00:03:18.260
we haven't designated a minimum approach temperature
for our heat exchangers.
00:03:18.260 --> 00:03:23.440
So the first step in using the temperature
interval method is to designate this minimum
00:03:23.440 --> 00:03:28.890
approach temperature for our design of our
heat exchangers, and a good starting point
00:03:28.890 --> 00:03:33.560
is going to be 10 degrees Celsius, and to
account for this in our energy balances we're
00:03:33.560 --> 00:03:39.750
going to take the hot streams, and we're going
to subtract this approach temperature from
00:03:39.750 --> 00:03:47.099
the temperatures from the hot streams, so
this becomes 170 and 50, 140 and 20.
00:03:47.099 --> 00:03:52.690
Now we maintain the temperatures for the cold
streams, and we take these temperatures, these
00:03:52.690 --> 00:03:57.299
adjusted temperatures, as the temperatures
that we're going to use to create our intervals.
00:03:57.299 --> 00:04:01.010
So a good place just to show where the streams
are is to draw a diagram of this where we
00:04:01.010 --> 00:04:09.739
label our temperatures that we saw from our
adjusted temperatures in order from coldest
00:04:09.739 --> 00:04:15.810
to hottest, and then we could draw arrows
to designate which stream overlaps these temperature
00:04:15.810 --> 00:04:16.810
intervals.
00:04:16.810 --> 00:04:23.229
So if we look at our cold stream, for C(1),
that goes from 30 to 135, we could draw an
00:04:23.229 --> 00:04:27.310
arrow that shows that shows that, and we could
do the same thing for our second cold stream
00:04:27.310 --> 00:04:28.860
that goes from 80 to 140.
00:04:28.860 --> 00:04:35.540
Now if we do this for our hot streams we have
one that goes from 140 to 30, and our other
00:04:35.540 --> 00:04:40.110
one that goes from 170 to 50, and I'll show
you why this is going to be important as we
00:04:40.110 --> 00:04:42.900
move further into this approach.
00:04:42.900 --> 00:04:47.860
Our next step is to draw a basic flow chart
that shows the transfer of energy in between
00:04:47.860 --> 00:04:50.009
each of these temperature intervals.
00:04:50.009 --> 00:04:54.470
So we start with the lowest temperature at
the bottom, and in between each of these boxes
00:04:54.470 --> 00:04:58.080
we'll write what the temperatures of those
intervals are.
00:04:58.080 --> 00:05:03.340
So the next step after this is to determine
the enthalpies of each interval, and to do
00:05:03.340 --> 00:05:11.220
that our equation for our change in enthalpy
is just going to be our heat capacity flow
00:05:11.220 --> 00:05:13.780
rate times our temperature difference.
00:05:13.780 --> 00:05:18.710
However, we have to account for all of the
streams, so I'll put a summation on here.
00:05:18.710 --> 00:05:23.870
This is where the chart comes in handy, if
we go back and look at our chart and we could
00:05:23.870 --> 00:05:29.120
fill in our information for the heat capacity
rate we could see for the interval of 140
00:05:29.120 --> 00:05:38.680
to 170 we have one stream that's involved,
so our delta H for the first process is just
00:05:38.680 --> 00:05:46.419
going to be 3 times the change in temperature,
which gives us 90 kW.
00:05:46.419 --> 00:05:52.270
Now for this second process we go back and
look at our chart, and we notice that we have
00:05:52.270 --> 00:05:58.360
three streams that are involved with this
interval, so we take the hot streams and we
00:05:58.360 --> 00:06:04.520
add up the heat capacities, that gives us
4, and we're going to subtract out the heat
00:06:04.520 --> 00:06:06.419
capacities of the cold streams.
00:06:06.419 --> 00:06:08.889
4-5 will give us negative 1.
00:06:08.889 --> 00:06:14.770
So I'll have negative 1 as our summation times
our interval, 5 degrees Celsius, and this
00:06:14.770 --> 00:06:16.900
gives us negative 5 kW.
00:06:16.900 --> 00:06:20.900
Now I'll do this for the rest of the temperature
intervals, and you could see the resulting
00:06:20.900 --> 00:06:23.190
enthalpies of those calculations.
00:06:23.190 --> 00:06:26.780
The next step is to calculate the residual
enthalpy, which is going to be a cumulative
00:06:26.780 --> 00:06:34.870
addition of all the intervals, so our residual
enthalpy starts with our 90 kW and then as
00:06:34.870 --> 00:06:40.190
we add the negative 5 we drop down to 85,
and so forth.
00:06:40.190 --> 00:06:43.760
So this gives us an idea of where the pinch
point of this process is going to be.
00:06:43.760 --> 00:06:48.660
Now this pinch point is defined such that
no energy is transferred across the pinch,
00:06:48.660 --> 00:06:55.280
and that's in order to maintain our approach
to minimize our utility loads.
00:06:55.280 --> 00:06:59.199
So at this point we're going to choose the
most negative enthlapy value, which is shown
00:06:59.199 --> 00:07:05.380
here, and we're going to take that as our
hot utility load and add it to the beginning
00:07:05.380 --> 00:07:07.819
of this block diagram.
00:07:07.819 --> 00:07:14.240
So we do a final pass through our temperature
intervals, where now we're going to start
00:07:14.240 --> 00:07:20.210
with 80 kW, we're going to add the enthalpies
from each temperature interval such that at
00:07:20.210 --> 00:07:24.069
a pinch point we have 0 as our value.
00:07:24.069 --> 00:07:33.569
What this does is tell us our eventual residual
enthalpy that's associated with our cold utility.
00:07:33.569 --> 00:07:38.919
So our hot utility was what we added to the
system to start, and now our cold utility
00:07:38.919 --> 00:07:44.690
is the bottom, and these values are our MER
targets.
00:07:44.690 --> 00:07:51.030
We've identified our pinch point to be 80
degrees for our cold stream, and because our
00:07:51.030 --> 00:07:56.640
minimum approach temperature was 10 degrees
our hot side is going to be 90.
00:07:56.640 --> 00:08:01.270
So the last part of this process is to do
what's known as a pinch decomposition of our
00:08:01.270 --> 00:08:05.780
hot and cold streams just to show what our
networks going to look like from start to
00:08:05.780 --> 00:08:09.319
finish before we put in any of the heat exchangers.
00:08:09.319 --> 00:08:14.690
So I've filled in the specific heat flow rates
on the right of each stream, and designated
00:08:14.690 --> 00:08:18.590
the hot streams going left to right, and the
cold stream's right to left.
00:08:18.590 --> 00:08:25.340
So we plug in our values for our pinch temperatures,
so on the cold side it's going to be 80 degrees,
00:08:25.340 --> 00:08:31.830
and on our hot side it's going to be 90 for
our pinch temperature, we'll fill in our source
00:08:31.830 --> 00:08:34.270
and target temperatures for each stream.
00:08:34.270 --> 00:08:40.560
So we use the actual values given in the problem
statement, so our hot stream starts at 180
00:08:40.560 --> 00:08:43.159
and finishes at 60.
00:08:43.159 --> 00:08:50.269
Our second hot stream starts at 150, finishes
at 30 degrees Celsius, our cold stream starts
00:08:50.269 --> 00:08:54.770
at 30 and finishes at 135.
00:08:54.770 --> 00:08:59.550
The other one starts at 80, and finishes at
140.
00:08:59.550 --> 00:09:03.680
Now what you can notice is that we have a
pinch temperature of 80, and our start temperature
00:09:03.680 --> 00:09:05.160
of 80.
00:09:05.160 --> 00:09:11.450
So this means that we can actually get rid
of this side altogether, and we have the second
00:09:11.450 --> 00:09:17.390
cold stream, C(2) only on the hot side of
the pinch, and we've designated this as our
00:09:17.390 --> 00:09:20.730
hot side, and this as our cold side.
00:09:20.730 --> 00:09:25.480
So we would at this point would move on to
designing our two heat exchanger networks,
00:09:25.480 --> 00:09:29.779
one for the hot side of the pinch, and one
for the cold side, and we'll do that in a
00:09:29.779 --> 00:09:31.539
subsequent screencast.
Office location
Engineering company LOTUS®
Russia, Ekaterinburg, Lunacharskogo street, 240/12

Phone: +7 343 216 77 75

E-mail: info@lotus1.ru

Sales phone

Russia: +7 343 216 77 75

WhatsApp: +79122710308