Top 10 Circulator Pump Problems Found on Boilers!

WEBVTT
Kind: captions
Language: en

00:00:01.579
hey guys this is Craig me who I trade
00:00:03.370 00:00:03.380 with EC silverstack and today we're
00:00:04.990 00:00:05.000 going over are the top ten problems that
00:00:06.700 00:00:06.710 occur with circulating pumps used for
00:00:08.709 00:00:08.719 boilers problem number one is if you
00:00:10.959 00:00:10.969 have air in the lines and it's actually
00:00:12.879 00:00:12.889 not the fault of the circulating pump so
00:00:15.220 00:00:15.230 the circulating pump could be running
00:00:16.689 00:00:16.699 just like this so I don't know if you
00:00:19.450 00:00:19.460 can hear that that noise right there you
00:00:21.220 00:00:21.230 could actually put a stethoscope on the
00:00:22.900 00:00:22.910 end of this or you can listen in with a
00:00:24.940 00:00:24.950 screwdriver to allow transmission of
00:00:28.480 00:00:28.490 that noise across the screwdriver over
00:00:30.640 00:00:30.650 to your ear you would definitely not
00:00:32.589 00:00:32.599 want to use a screw driver or anything
00:00:33.790 00:00:33.800 like that if there is exposed parts that
00:00:36.460 00:00:36.470 we're turning but everything's
00:00:37.450 00:00:37.460 internally moving inside this pump right
00:00:39.670 00:00:39.680 now and you can tell that the that the
00:00:42.040 00:00:42.050 circulator pump is running where at
00:00:44.500 00:00:44.510 least that the motor is running so then
00:00:47.110 00:00:47.120 comes the problem of having to purge the
00:00:49.210 00:00:49.220 air into the lines so in order to get
00:00:51.400 00:00:51.410 the air out of the lines most boilers
00:00:53.470 00:00:53.480 are going to have an automatic air bleed
00:00:55.180 00:00:55.190 so such as this so as long as this calf
00:00:57.549 00:00:57.559 is loose it's gonna automatically get
00:00:59.470 00:00:59.480 the air out of the system if you find
00:01:01.660 00:01:01.670 that this cap is tight on the boiler
00:01:03.459 00:01:03.469 there may be a reason for that and that
00:01:04.840 00:01:04.850 may be because the the valve at the top
00:01:07.059 00:01:07.069 right here may be leaking water out
00:01:08.919 00:01:08.929 instead of just purging the air and then
00:01:10.809 00:01:10.819 stopping so in that case you may have to
00:01:13.419 00:01:13.429 replace the the valve core in the inside
00:01:16.179 00:01:16.189 here or go ahead and replace the
00:01:18.609 00:01:18.619 automatic air bleed some are not fitted
00:01:20.980 00:01:20.990 with a valve core and they just have a a
00:01:22.779 00:01:22.789 piece of rubber that blocks the port but
00:01:25.209 00:01:25.219 basically just valve that off take the
00:01:26.709 00:01:26.719 pressure off and then you go ahead and
00:01:28.179 00:01:28.189 replace this you could also have a venti
00:01:30.099 00:01:30.109 that's inside the baseboard and
00:01:31.629 00:01:31.639 basically at the top here you'd have
00:01:33.429 00:01:33.439 either a Schrader valve or you'd have a
00:01:35.410 00:01:35.420 key valve and when you what you do is
00:01:38.139 00:01:38.149 you loosen that up if it's a key valve
00:01:39.999 00:01:40.009 and it lets air out and water until you
00:01:42.969 00:01:42.979 get a steady stream of water coming out
00:01:45.010 00:01:45.020 then you go ahead and tighten it back up
00:01:46.089 00:01:46.099 or it could just have a Schrader valve
00:01:48.399 00:01:48.409 in it so so that's something that you
00:01:50.559 00:01:50.569 could use to get the air out of the the
00:01:52.569 00:01:52.579 lines up at the high points of the
00:01:54.609 00:01:54.619 baseboard radiators you could also use
00:01:56.679 00:01:56.689 your boiler drains say you have a boiler
00:01:58.959 00:01:58.969 drain on the supply side in the boiler
00:02:01.269 00:02:01.279 drain on the return side and say maybe
00:02:03.279 00:02:03.289 have tsums
00:02:04.209 00:02:04.219 what you can do is you can open up one
00:02:06.399 00:02:06.409 hook it to a hose and then attach this
00:02:08.589 00:02:08.599 to your cold water and you can force
00:02:10.780 00:02:10.790 cold water through with the other boiler
00:02:13.240 00:02:13.250 drain open and then base
00:02:15.040 00:02:15.050 we are going to allow air coming out and
00:02:17.230 00:02:17.240 you're going to allow the water coming
00:02:18.490 00:02:18.500 out until the gurgling of water mixed
00:02:21.460 00:02:21.470 with air stops so you just have a steady
00:02:23.050 00:02:23.060 stream of water so you do that for each
00:02:25.450 00:02:25.460 zone until you have all the air out of
00:02:27.880 00:02:27.890 the lines you want to make sure that you
00:02:29.080 00:02:29.090 don't exceed the max pressure while
00:02:30.850 00:02:30.860 you're doing that on the system because
00:02:32.170 00:02:32.180 you don't want the pressure at least to
00:02:33.430 00:02:33.440 blow the other thing that you could do
00:02:34.930 00:02:34.940 is if you have a boiler drain on the
00:02:36.610 00:02:36.620 opposite side as the where the cold
00:02:39.370 00:02:39.380 water feeds in you have this backflow
00:02:41.320 00:02:41.330 preventor and pressure reducing valve
00:02:42.880 00:02:42.890 you can just allow this to push the
00:02:44.590 00:02:44.600 water in and then vent the air out of
00:02:46.930 00:02:46.940 the other side with your boiler drain
00:02:48.130 00:02:48.140 until you have a steady stream of water
00:02:49.410 00:02:49.420 when you're done purging the air out of
00:02:51.430 00:02:51.440 lines you want to make sure that you're
00:02:52.570 00:02:52.580 back down to 12 to 15 psi G with a cold
00:02:56.500 00:02:56.510 working pressure on that boiler when the
00:02:58.810 00:02:58.820 boiler is hot it's probably gonna be
00:03:00.130 00:03:00.140 around 18 to 22 psi G so this pressure
00:03:03.820 00:03:03.830 reducing valve is what allows water to
00:03:06.520 00:03:06.530 feed into the system to keep it at a
00:03:08.920 00:03:08.930 steady cold water temperature of 12 to
00:03:11.770 00:03:11.780 15 psi G Robin number two could be if
00:03:14.620 00:03:14.630 you have some type of a blockage in the
00:03:16.450 00:03:16.460 system and it's not allowing the water
00:03:18.370 00:03:18.380 to flow freely so that could be a manual
00:03:21.760 00:03:21.770 valve such as one of these right here it
00:03:24.250 00:03:24.260 could be an automatic electrical valve
00:03:26.650 00:03:26.660 or it could be something like this and
00:03:28.660 00:03:28.670 this is a mixing valve and on the sides
00:03:30.910 00:03:30.920 of some mixing valves you're gonna have
00:03:33.160 00:03:33.170 a screen inside and that can end up
00:03:35.290 00:03:35.300 getting clogged up so this is a washer
00:03:38.199 00:03:38.209 with a screen a lot of newer ones don't
00:03:40.360 00:03:40.370 have those but some do and so that can
00:03:43.270 00:03:43.280 end up clogging up problem number three
00:03:46.030 00:03:46.040 is if the motor is stuck and it's just
00:03:48.400 00:03:48.410 not turning the impeller inside so this
00:03:50.800 00:03:50.810 is probably one of the most common
00:03:52.300 00:03:52.310 issues is when the bearings end up
00:03:54.160 00:03:54.170 seizing up inside the system so this
00:03:56.680 00:03:56.690 circular pump are going to take an amp
00:03:58.000 00:03:58.010 draw and this one is working and then
00:04:00.490 00:04:00.500 we're going to take a AM throw on
00:04:01.780 00:04:01.790 another one that is not working so we
00:04:03.970 00:04:03.980 have our ECM clamp clamped around one
00:04:06.250 00:04:06.260 wire and it's reading 0.65 and also
00:04:09.670 00:04:09.680 realizing that there's no load in here
00:04:11.259 00:04:11.269 right now as far as the water goes this
00:04:14.860 00:04:14.870 pump right here on the rating plate
00:04:17.349 00:04:17.359 states 0.71 amps so this motor right
00:04:21.280 00:04:21.290 here is stuck in is not turning the
00:04:22.990 00:04:23.000 impeller will not turn and unfortunately
00:04:25.930 00:04:25.940 there's no access in order to try to
00:04:27.670 00:04:27.680 help it turn
00:04:28.660 00:04:28.670 but that also means that the bearings
00:04:30.190 00:04:30.200 are very seized up inside and they're
00:04:33.220 00:04:33.230 just stuck in place so let's go ahead
00:04:35.260 00:04:35.270 and take an amp draw and you can see
00:04:36.940 00:04:36.950 that this amp draw is right about twice
00:04:40.090 00:04:40.100 as much as this one was running it it's
00:04:42.940 00:04:42.950 actually a little bit over that but it's
00:04:44.530 00:04:44.540 at one point three five amps right there
00:04:46.690 00:04:46.700 so you can actually hear the difference
00:04:48.580 00:04:48.590 between a running pump such as this one
00:04:50.620 00:04:50.630 right here and a non running pump so
00:04:53.230 00:04:53.240 there is no water sloshing there's no
00:04:55.330 00:04:55.340 noise at all other than just a humming
00:04:57.880 00:04:57.890 noise because the windings are basically
00:05:00.490 00:05:00.500 overheating and it's not working
00:05:03.760 00:05:03.770 properly the rotor is not turning in
00:05:06.520 00:05:06.530 reference to the crew and foss bumps you
00:05:08.230 00:05:08.240 could use either a very wide screwdriver
00:05:10.300 00:05:10.310 or you could use a quarter I like to use
00:05:12.460 00:05:12.470 a pair of vise grips and then you can go
00:05:13.990 00:05:14.000 ahead and turn it like that or you could
00:05:15.490 00:05:15.500 also use the screwdriver with the vise
00:05:18.040 00:05:18.050 grips just in order to press downwards
00:05:19.810 00:05:19.820 and then you can go ahead and turn it
00:05:21.280 00:05:21.290 like that but you don't want to use a
00:05:22.990 00:05:23.000 thin screwdriver because you're going to
00:05:25.180 00:05:25.190 end up marking up or bending this the
00:05:28.540 00:05:28.550 screw right here and possibly damaging
00:05:30.790 00:05:30.800 it and then not being able to turn it as
00:05:32.320 00:05:32.330 you can see somebody has already done
00:05:33.670 00:05:33.680 that on this screw so you can see in the
00:05:44.320 00:05:44.330 end right here and you can actually get
00:05:45.940 00:05:45.950 to the end of the rotor in order to see
00:05:48.010 00:05:48.020 if it's going to turn or not so if it's
00:05:50.200 00:05:50.210 if it's real hard or something like that
00:05:52.030 00:05:52.040 and it's not turning very well that
00:05:54.340 00:05:54.350 could be an issue right there or if it's
00:05:56.380 00:05:56.390 just not turning it all and it's
00:05:57.400 00:05:57.410 completely stuck so this right here you
00:06:01.270 00:06:01.280 can get to from the end and also if you
00:06:03.700 00:06:03.710 took these four bolts off you can get to
00:06:05.890 00:06:05.900 the full rotor assembly in order to be
00:06:07.840 00:06:07.850 able to turn them so you gonna notice a
00:06:09.670 00:06:09.680 rubber o-ring right here and that is
00:06:11.950 00:06:11.960 actually holding the water in there
00:06:13.450 00:06:13.460 because water does come into there in
00:06:15.760 00:06:15.770 order to help the sleeve bearings
00:06:18.130 00:06:18.140 operate so you want to be aware of that
00:06:20.680 00:06:20.690 before opening this up now show you what
00:06:24.190 00:06:24.200 this one looks like in a second because
00:06:26.050 00:06:26.060 what we'll do is we'll unscrew these
00:06:28.510 00:06:28.520 four bolts right here and we'll be able
00:06:31.060 00:06:31.070 to take this motor right off of here and
00:06:33.730 00:06:33.740 we'll be able to check the impeller on
00:06:36.490 00:06:36.500 this right here
00:06:38.320 00:06:38.330 you should have valve somewhere as close
00:06:40.330 00:06:40.340 to the circulating pump if you need to
00:06:42.130 00:06:42.140 replace
00:06:42.700 00:06:42.710 the motor instead of the actual pump
00:06:46.480 00:06:46.490 housing but on these water will come out
00:06:49.990 00:06:50.000 when you go to replace that motor right
00:06:51.939 00:06:51.949 there so you want to go ahead and valve
00:06:53.620 00:06:53.630 off on both sides so go ahead and
00:06:56.620 00:06:56.630 unscrew these they're not going to be
00:07:00.430 00:07:00.440 that that tight so you should be able to
00:07:02.050 00:07:02.060 get them loose fairly easily you have to
00:07:07.930 00:07:07.940 unscrew them all the way out I'm just
00:07:09.310 00:07:09.320 breaking them loose right now
00:07:17.840 00:07:17.850 now this just fell apart but just one
00:07:20.850 00:07:20.860 tap with a flathead screwdriver and this
00:07:22.740 00:07:22.750 should come apart and as you can see
00:07:25.260 00:07:25.270 right here we have our impeller and it
00:07:27.420 00:07:27.430 is not turning at all okay so it's it's
00:07:32.100 00:07:32.110 frozen solid
00:07:33.210 00:07:33.220 so that's your bearings and your sleeve
00:07:35.850 00:07:35.860 right there or holding on to that axle
00:07:40.730 00:07:40.740 here's another one right here and you
00:07:42.840 00:07:42.850 can see that this one spins freely so if
00:07:47.730 00:07:47.740 you have the circulating pump out such
00:07:49.740 00:07:49.750 as this right here you can just go ahead
00:07:52.170 00:07:52.180 and take a screwdriver in there and see
00:07:54.060 00:07:54.070 if you can push on the empower and see
00:07:56.700 00:07:56.710 if you can get it to spin so as you can
00:07:58.710 00:07:58.720 see it's fairly easy to replace a
00:08:00.090 00:08:00.100 circulating pump motor off of a
00:08:02.460 00:08:02.470 circulating pump flange such as this so
00:08:05.130 00:08:05.140 what you want to do is you want to go
00:08:06.510 00:08:06.520 ahead and valve off before and after the
00:08:08.820 00:08:08.830 circulating pump and then under your
00:08:10.650 00:08:10.660 four bolts you pull this off and you
00:08:12.660 00:08:12.670 want to replace this little o-ring right
00:08:15.180 00:08:15.190 here then you bolt your new one on and
00:08:17.010 00:08:17.020 then you got to turn your electrical
00:08:18.500 00:08:18.510 power off and replace your electrical
00:08:21.510 00:08:21.520 wiring and then you're ready to go and
00:08:23.280 00:08:23.290 then you can go ahead and turn the
00:08:24.060 00:08:24.070 system back on again so after you
00:08:25.950 00:08:25.960 replaced the motor if you get your water
00:08:27.960 00:08:27.970 level all the way up to here then all
00:08:30.570 00:08:30.580 you have to do is purge this amount of
00:08:32.070 00:08:32.080 air out versus this amount of air that
00:08:34.920 00:08:34.930 would be a lot harder so it just depends
00:08:37.500 00:08:37.510 on where your air bleeds are at in the
00:08:40.050 00:08:40.060 system as far as how hard it is to get
00:08:42.450 00:08:42.460 your air out now you could have a larger
00:08:45.090 00:08:45.100 circulating pump such as this and you
00:08:47.370 00:08:47.380 have bearings multiple bearings that you
00:08:48.930 00:08:48.940 need to wheel on this twice a season so
00:08:51.300 00:08:51.310 right here is an oil port here's an oil
00:08:53.340 00:08:53.350 port and here's an oil port and either
00:08:56.250 00:08:56.260 the motor could go bad or you could be
00:08:59.040 00:08:59.050 over here in this assembly where the the
00:09:01.860 00:09:01.870 motor attaches to the impeller acts a
00:09:04.470 00:09:04.480 lot so any of those bearings could be
00:09:07.200 00:09:07.210 the problem but they do have to get
00:09:08.970 00:09:08.980 wheeled on on a circulating pump such as
00:09:11.670 00:09:11.680 this problem number four can be if you
00:09:14.700 00:09:14.710 have something jammed up inside the
00:09:16.590 00:09:16.600 impeller area so something could be
00:09:19.110 00:09:19.120 breaking loose from inside the system
00:09:21.390 00:09:21.400 and in this case you see it is a rubber
00:09:23.310 00:09:23.320 o-ring that's stuck in the impeller in
00:09:26.610 00:09:26.620 there so that would stop the motor from
00:09:29.319 00:09:29.329 turning or stop it from turning as
00:09:31.509 00:09:31.519 quickly so that could be an issue
00:09:33.819 00:09:33.829 as you can see the impellers are not
00:09:37.090 00:09:37.100 tight up against the inside of here so
00:09:40.619 00:09:40.629 it really takes something large in order
00:09:43.479 00:09:43.489 to stop this from from turning so
00:09:46.059 00:09:46.069 there's a lot of free space in there so
00:09:49.600 00:09:49.610 this is more of a rarer instance but
00:09:52.359 00:09:52.369 it's still something that can happen
00:09:53.729 00:09:53.739 problem number five is if you are
00:09:56.079 00:09:56.089 leaking water out of the side where the
00:09:58.389 00:09:58.399 motor mounts over to the impeller flange
00:10:01.299 00:10:01.309 assembly so as you can see right here
00:10:03.910 00:10:03.920 there's a rubber o-ring rate along the
00:10:06.309 00:10:06.319 inside here sometimes it's set back in
00:10:08.769 00:10:08.779 this instance it's right along the edge
00:10:10.720 00:10:10.730 and on this one you can see that the
00:10:13.900 00:10:13.910 water was leaking outside of it and you
00:10:17.079 00:10:17.089 see that this rubber o-ring right here
00:10:19.509 00:10:19.519 had fallen off and broke so this can
00:10:22.239 00:10:22.249 happen just due to that the each or the
00:10:25.479 00:10:25.489 titanosaur or something like that and
00:10:27.669 00:10:27.679 you just need to replace the o-ring
00:10:29.979 00:10:29.989 itself another thing could be just that
00:10:32.919 00:10:32.929 these screws are not tight enough and
00:10:34.869 00:10:34.879 that could have been the problem the
00:10:37.989 00:10:37.999 same thing on this circulating pump do
00:10:39.609 00:10:39.619 you have a gasket right along the inside
00:10:41.650 00:10:41.660 here and that could have worn down or
00:10:44.530 00:10:44.540 the the bolts may not have been tight
00:10:46.179 00:10:46.189 enough so it could be leaking water out
00:10:47.710 00:10:47.720 of there you could also have a problem
00:10:50.229 00:10:50.239 such as at these gaskets right here and
00:10:52.960 00:10:52.970 right here these would be outside of the
00:10:54.549 00:10:54.559 pump assembly but what could have
00:10:56.169 00:10:56.179 happened is maybe one of these bolts and
00:10:58.569 00:10:58.579 that's where tighten down to hard
00:11:00.100 00:11:00.110 compared to the other side or maybe this
00:11:01.539 00:11:01.549 got squished and cracked over time or
00:11:03.970 00:11:03.980 maybe the cast iron cracked and broke
00:11:06.970 00:11:06.980 because the the bolts were too tight or
00:11:09.249 00:11:09.259 maybe the nut has loosened up over time
00:11:11.499 00:11:11.509 so that's a variety of things that that
00:11:13.749 00:11:13.759 could allow water to leak out of this
00:11:16.479 00:11:16.489 gasket area problem number six could be
00:11:19.119 00:11:19.129 that even though your thermostats
00:11:20.590 00:11:20.600 calling for heat you may not have power
00:11:23.229 00:11:23.239 getting to your circulating pump so you
00:11:25.600 00:11:25.610 could have incorrect power or no power
00:11:28.329 00:11:28.339 at all to your circulating pump and
00:11:29.859 00:11:29.869 that's why you don't have any hot water
00:11:31.359 00:11:31.369 so on aqua stat relay such as this these
00:11:34.659 00:11:34.669 contacts inside could be pitted so when
00:11:37.989 00:11:37.999 this is calling for the circulating pump
00:11:40.749 00:11:40.759 to run to circulate your Heat
00:11:43.210 00:11:43.220 it's supposed to suck this relay down
00:11:44.770 00:11:44.780 and these contacts become pitted and
00:11:46.750 00:11:46.760 sometimes you'll have a high resistance
00:11:48.340 00:11:48.350 value across them and then you won't
00:11:49.720 00:11:49.730 have your power coming in here and going
00:11:53.260 00:11:53.270 over to here so this this relay right
00:11:56.110 00:11:56.120 here is stopping your hop from
00:11:57.790 00:11:57.800 connecting to the hop that comes out of
00:11:59.680 00:11:59.690 this aqua Staten goes to your
00:12:02.260 00:12:02.270 circulating poem you can also have
00:12:04.900 00:12:04.910 something like this and this is a zone
00:12:06.910 00:12:06.920 control relay right here and the
00:12:09.580 00:12:09.590 circulating pump is powered via this end
00:12:12.280 00:12:12.290 switch down here so the switch is
00:12:14.470 00:12:14.480 exactly what it is it's it's a switch
00:12:16.570 00:12:16.580 it's a normally open switch so that's
00:12:18.760 00:12:18.770 the extra end switch and this is the
00:12:20.710 00:12:20.720 main end switch so you come into here
00:12:23.530 00:12:23.540 with power and you connect it to your
00:12:25.480 00:12:25.490 transformer so that this board can be
00:12:27.730 00:12:27.740 powered first of all then you have a
00:12:29.770 00:12:29.780 power coming out and then going over to
00:12:32.650 00:12:32.660 this switch and then coming out of the
00:12:35.500 00:12:35.510 switches the hot that goes to your
00:12:37.090 00:12:37.100 circulating pump and so this switch will
00:12:39.880 00:12:39.890 not close the electrical circuit until
00:12:42.910 00:12:42.920 the thermostat calls so you have 24
00:12:46.060 00:12:46.070 volts going to a thermostat coming back
00:12:48.400 00:12:48.410 to the board right here
00:12:50.980 00:12:50.990 sending a call for heat then you have
00:12:53.080 00:12:53.090 your zone valve you see 2 to 3 either
00:12:57.040 00:12:57.050 has to have continuity or 3 to 4 has to
00:12:59.050 00:12:59.060 have continuity in order for this board
00:13:01.870 00:13:01.880 to send power there to the circulating
00:13:04.090 00:13:04.100 pump that confirms that the zone valve
00:13:07.600 00:13:07.610 is mechanically open and the water will
00:13:11.380 00:13:11.390 flow if your circulating pump turns on
00:13:13.230 00:13:13.240 so you can have an issue with this
00:13:15.790 00:13:15.800 you could have an issue with bad
00:13:17.800 00:13:17.810 contacts and your aqua stop or just the
00:13:20.350 00:13:20.360 aqua stat itself is not sending power
00:13:22.210 00:13:22.220 over to your circulating boat but you
00:13:24.790 00:13:24.800 can measure for your voltage right here
00:13:26.650 00:13:26.660 by turning your multimeter on to voltage
00:13:28.960 00:13:28.970 and then you can put one probe in one
00:13:31.750 00:13:31.760 wire nut and one on the other one in
00:13:33.160 00:13:33.170 order to read if you're reading 120
00:13:35.290 00:13:35.300 volts or not problem number seven could
00:13:37.690 00:13:37.700 be if the motor electrical windings are
00:13:39.850 00:13:39.860 bad so a way to check that is you just
00:13:43.180 00:13:43.190 turn the power off you disconnect the
00:13:45.490 00:13:45.500 electrical wires and they can check the
00:13:46.870 00:13:46.880 resistance value of the electrical motor
00:13:49.600 00:13:49.610 windings so right now right now we have
00:13:52.720 00:13:52.730 the multimeter set on ohms and we're
00:13:54.820 00:13:54.830 reading 42
00:13:55.950 00:13:55.960 2.2 ohms of resistance so if we read oh
00:13:59.580 00:13:59.590 well like we do right now then that
00:14:01.680 00:14:01.690 means that the windings have burnt apart
00:14:03.680 00:14:03.690 likewise if we check right over here to
00:14:06.780 00:14:06.790 the ground we should have no resistance
00:14:09.030 00:14:09.040 whatsoever if we did and that means that
00:14:10.830 00:14:10.840 the motor windings have burnt apart and
00:14:13.170 00:14:13.180 are touching the the metal ground frame
00:14:17.750 00:14:17.760 so you can see that that motor is good
00:14:22.250 00:14:22.260 now just because our wire is connected
00:14:26.520 00:14:26.530 to the capacitor it's in a buck
00:14:28.290 00:14:28.300 connector you don't have to cut that out
00:14:30.120 00:14:30.130 in order to check your resistance value
00:14:31.710 00:14:31.720 we are checking the true resistance
00:14:34.650 00:14:34.660 value right now of 42 ohms it's taking
00:14:37.680 00:14:37.690 the path of least resistance that's why
00:14:39.360 00:14:39.370 it's not going through that capacitor so
00:14:41.550 00:14:41.560 I'll show you that so on this one right
00:14:43.680 00:14:43.690 here the buck connector is cut out and
00:14:45.720 00:14:45.730 you see that we're still reading roughly
00:14:48.150 00:14:48.160 42 ohms of resistance on this one is
00:14:49.890 00:14:49.900 reading 41.3 ohms so this motor is good
00:14:53.910 00:14:53.920 problem number eight could be a bad
00:14:55.710 00:14:55.720 capacitor so what I did to replicate
00:14:58.140 00:14:58.150 that as I unwind this from the buck
00:15:00.150 00:15:00.160 connector between the black wire the red
00:15:02.310 00:15:02.320 wire and the white wire so this is
00:15:04.590 00:15:04.600 disconnected and we're gonna go ahead
00:15:06.090 00:15:06.100 and put our our multimeter on our hot
00:15:09.540 00:15:09.550 wire right here and it's set on amperage
00:15:11.550 00:15:11.560 right now and we're gonna go ahead and
00:15:12.750 00:15:12.760 turn the power on and see what happens
00:15:14.310 00:15:14.320 when you have either a back capacitor
00:15:16.680 00:15:16.690 that where the capacitor is not attached
00:15:18.810 00:15:18.820 to a PSE motor for a circulating pump so
00:15:23.790 00:15:23.800 right now we're reading 1.5 amps and we
00:15:26.730 00:15:26.740 do not see the impeller turning so this
00:15:30.150 00:15:30.160 is the same ampere treating we read when
00:15:31.770 00:15:31.780 the bearings were locked and the
00:15:33.600 00:15:33.610 capacitor was good now the power is off
00:15:36.960 00:15:36.970 I'm going to go ahead and wire this
00:15:39.360 00:15:39.370 black wire right back in
00:15:50.950 00:15:50.960 and then we'll go ahead and turn the
00:15:53.210 00:15:53.220 power back on and now you see we're only
00:15:57.350 00:15:57.360 drawing 0.7 amps and the motor is
00:16:00.080 00:16:00.090 running so in order to test the
00:16:06.380 00:16:06.390 capacitor you want to shut the power off
00:16:07.850 00:16:07.860 and go ahead and disconnect the wires
00:16:10.100 00:16:10.110 and then what you do is you cut the buck
00:16:12.740 00:16:12.750 connector that was connecting these
00:16:14.780 00:16:14.790 three wires cut that out and then you
00:16:17.000 00:16:17.010 can go ahead and take your capacitor
00:16:19.070 00:16:19.080 wire in order to read the UF reading on
00:16:21.830 00:16:21.840 the capacitor you have to short the
00:16:23.630 00:16:23.640 capacitor out so you take this wire and
00:16:25.520 00:16:25.530 you touch the other end of the wire down
00:16:27.080 00:16:27.090 here and once you do that we can go
00:16:31.070 00:16:31.080 ahead and read it with our multimeter so
00:16:34.940 00:16:34.950 we're going to turn our multimeter on
00:16:37.850 00:16:37.860 and we're going to go ahead and hit the
00:16:39.230 00:16:39.240 Select until we get to UF so then we
00:16:44.120 00:16:44.130 take one probe that has the alligator
00:16:47.900 00:16:47.910 clip we'll connect it right on there
00:16:49.390 00:16:49.400 make sure it doesn't touch any other
00:16:51.320 00:16:51.330 wires and then we'll touch the metal
00:16:53.090 00:16:53.100 part where it's connected down there in
00:16:54.910 00:16:54.920 order to get our MFD reading so on this
00:16:58.790 00:16:58.800 one we're reading 2.01 and on the
00:17:03.260 00:17:03.270 capacitor it says it's a 5 UF so the
00:17:06.800 00:17:06.810 motor may run but it's not as healthy
00:17:09.260 00:17:09.270 for the motor to have this capacitor in
00:17:12.439 00:17:12.449 place because this this is definitely
00:17:14.689 00:17:14.699 less or actually it's it's more off than
00:17:17.600 00:17:17.610 5% so it's it's less than half of what
00:17:21.110 00:17:21.120 the rating is now go ahead and short
00:17:23.449 00:17:23.459 this one just like we did the other one
00:17:24.770 00:17:24.780 so we just go ahead and touch this wire
00:17:26.210 00:17:26.220 down in here and then we'll put our
00:17:28.610 00:17:28.620 alligator clip on and make sure our
00:17:34.520 00:17:34.530 probes are not touching anything other
00:17:35.870 00:17:35.880 than the wire and you see that that
00:17:38.480 00:17:38.490 one's reading 4.9 2 3 so that one is
00:17:41.480 00:17:41.490 good that's within 5% of the reading so
00:17:44.090 00:17:44.100 it's the same same reading on this one
00:17:45.770 00:17:45.780 says 5 UF plus or minus 5% problem
00:17:51.980 00:17:51.990 number 9 could be if the axle is broke
00:17:54.980 00:17:54.990 off and so that the motor rotor is not
00:17:57.770 00:17:57.780 connected to the impeller
00:18:00.100 00:18:00.110 so you know this is the inside rotor
00:18:02.530 00:18:02.540 assembly that goes inside the stator and
00:18:05.020 00:18:05.030 this is inside of this motor so what
00:18:09.070 00:18:09.080 could happen is this could end up
00:18:10.900 00:18:10.910 breaking so you see that this should not
00:18:13.090 00:18:13.100 be able to turn as this turns these
00:18:16.840 00:18:16.850 these stay still and this should turn
00:18:20.200 00:18:20.210 just like this and that's how it works
00:18:22.470 00:18:22.480 so you see that now though that this is
00:18:25.480 00:18:25.490 broken on the inside here so that could
00:18:29.950 00:18:29.960 happen so this right here is not metal
00:18:31.840 00:18:31.850 on these you see this right here it
00:18:37.270 00:18:37.280 could just snap so that could be an
00:18:39.010 00:18:39.020 issue now on a pump such as this right
00:18:41.530 00:18:41.540 here you could have separation between
00:18:43.720 00:18:43.730 the motor and the impeller so if you
00:18:46.720 00:18:46.730 look in here you'll see the coupling
00:18:49.150 00:18:49.160 that attaches both axles right there and
00:18:51.640 00:18:51.650 you see the springs that are attached
00:18:52.900 00:18:52.910 now you could have the rubber mount
00:18:54.820 00:18:54.830 inside going bad and and basically
00:18:58.660 00:18:58.670 breaking the the coupling assembly
00:19:00.610 00:19:00.620 because the axles are out of line or you
00:19:03.250 00:19:03.260 could have a weak spring or something
00:19:05.140 00:19:05.150 like that and they snap and then it's no
00:19:07.840 00:19:07.850 longer connected so that could be the
00:19:10.150 00:19:10.160 problem so you just rectify that by
00:19:12.010 00:19:12.020 taking these bolts off in order to
00:19:14.500 00:19:14.510 replace the coupling assembly and
00:19:15.910 00:19:15.920 possibly the rubber mount inside
00:19:18.180 00:19:18.190 problem number 10 could be a loud noise
00:19:20.500 00:19:20.510 coming from your circulating pump now
00:19:22.420 00:19:22.430 it's typically not from your impeller
00:19:24.160 00:19:24.170 it's typically from your bearings unless
00:19:26.080 00:19:26.090 you hear water gurgling or if that's the
00:19:28.900 00:19:28.910 kind of noise but if it's a squealing
00:19:30.460 00:19:30.470 noise it's typically the bearings inside
00:19:33.340 00:19:33.350 inside the the motor assembly now in
00:19:36.670 00:19:36.680 this case right here these have to be
00:19:38.230 00:19:38.240 oiled so if you don't wheel these
00:19:39.670 00:19:39.680 bearings those bearings are going to
00:19:42.070 00:19:42.080 deteriorate and you're gonna hear a
00:19:43.360 00:19:43.370 squealing noise from those if you hear
00:19:45.220 00:19:45.230 like a chattering noise something like
00:19:48.130 00:19:48.140 that that could be from the coupling
00:19:50.860 00:19:50.870 assembly that's inside of here so that
00:19:53.380 00:19:53.390 wouldn't need to be addressed if you're
00:19:54.760 00:19:54.770 looking for the multimeter I use in the
00:19:56.020 00:19:56.030 video or the other tools I use out in
00:19:57.460 00:19:57.470 the field I have them all linked down in
00:19:59.140 00:19:59.150 the description section below if you
00:20:00.910 00:20:00.920 want to help support this HVAC our
00:20:02.320 00:20:02.330 training channel click here if you want
00:20:03.700 00:20:03.710 to subscribe click here and if you want
00:20:05.050 00:20:05.060 to see another HVAC our training video
00:20:06.640 00:20:06.650 click right here hope you enjoyed
00:20:08.200 00:20:08.210 yourself and we'll see you next time at
00:20:09.310 00:20:09.320 AC service tech Channel
Office location
Engineering company LOTUS®
Russia, Ekaterinburg, Lunacharskogo street, 240/12

Phone: +7 343 216 77 75

E-mail: info@lotus1.ru

Sales phone

Russia: +7 343 216 77 75

WhatsApp: +79122710308